• Split Sky Air • Outdoor Units
23
• Outdoor Units • R-410A • RXS-G2V1B
4
Capacity tables
4 - 1 Cooling/Heating capacity tables
3
4
FFQRXS50G2V1B
Cooling
50Hz 230V
AFR
12.0
BF
0.16
Indoor
Outdoor temperature (°CDB)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
Heating
50Hz 230V
AFR
12.0
Indoor
Outdoor temperature (°CWB)
EDB
-15
-10
-5
0
6
10
(°C)
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
3D041023
SYMBOLS
AFR:
Air flow rate
(m
3
/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°C)
EDB:
Entering dry bulb temp.
(°C)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
NOTES
1
Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2
shows nominal (rated) capacities and power input.
3
TC, PI and SHC must be calculated by interpolation using the figures
in the above tables. (Figures out of the tables should not be used for
calculation.)
4
SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
=0.02*AFR(m3/min.)*(1-BF)*(DB*-EDB)
Add SHC* to SHC.
5
Capacities are based on following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6
Air flow rate (AFR) and Bypass factor (BF) are taburated above.