Daikin Quaternity H-Series Скачать руководство пользователя страница 75

Optional Accessories

EDUS04-906_b

74

Room Air Conditioners H-Series

Wiring

1. Wiring

Connect one end of the wiring to connector S21 of the PCB in the
indoor unit.

Connect the other end of the wiring to connector S6 of the adaptor
PCB.

Connect field wiring according to the functions assigned to each
connection terminal of the adaptor PCB.

Secure all wires.

1

Securing wires in the adaptor case assy (for KRP413A1S · KRP413AA1S)

Fasten with a tie-wrap so that wires will not come loose even if pulled.

Inter unit 
cable (field wiring)

Tie-wrap 
(to prevent the wires from coming loose)

If the wire protrudes from 
this side, cut the cut-off 
section of the case front.

2

Securing wires in the indoor unit (for KRP413A1)

The method for securing wire varies depending on the model of the air
conditioner. See your air conditioner installation manual for details.

2. Automatic Reset After Power Failure

This PCB stores the following data in the event of a power failure
(common features).

On/Off (see Note 1)

Operation modes

Temperature setting

Air flow rate

On/Off status of remote controller

(Note 1 When SW1-2 is in Off mode, the unit will not be activated.)

3. Monitor Signal Output (normal operation and malfunction)

Maximum length of the wiring is 100 m.

1

Monitor signal output for LED

LED

D

R

1

2

S

4

Max 100 m

2

Monitor signal output (normal operation and

         malfunction)using external relay contacts

DC12V

MR1

MR2

L

1

2

L

MR1

MR2

L

1

2

L

: Operation light

: Malfunction light

+

(+)

(–)

(–)

1

2

3

S
8

S
5

Max 100 m

Field supplied parts

External power 
supply for light

Field procured parts (Recommended external relay contacts)

Manufacturer

Type

Coil rated voltage

Coil resistance

Omron

MY relay

12 V DC

160 ohm ± 10%

Matsushita

HC relay

12 V DC

160 ohm ± 10%

4. Connection with Remote Controller

Example connections with three kinds of remote controllers are shown
bellow.

Note: These connections cannot be used in combination.

1

Generic remote controller

Set SW1-1 to Off and select Operation Mode 1.

SW1

ON

OFF

1

2

<Instantaneous Contact>

1

2

1

2

S
2

S
1

On/Off

Off

<Normal Contact>

1

2

1

2

S
1

S
2

Operation

On

2

Five-room central controller (KRC72)

Set SW1-1 to Off and select Operation Mode 1.

The remote controller most recently used takes precedence.

Five-room central

controller

Terminal

blocks A to E

1

2

3

4

1

2

1

2

1

2

SW1

ON

OFF

S
4

S
1

3

Fan coil remote controller

Set SW1-1 to On and select Operation Mode 2.

Most settings (power On/Off, air flow rate, mode change) cannot be
made using the air conditioner’s remote controller.

When power is restored after a power failure in this mode, On or Off is
determined according to the current settings of the remote controller.

When the Cooling /Heating mode is changed, use the air conditioner’s
remote controller to adjust the temperature.

1

2

SW1

ON

OFF

S
1

1

2

1

2

1

2

S
2

S
3

H M L OFF

Fan coil remote controller

Off

(When cooling)

On (When heating)

Cooling/heating switch

Locally procured parts

Item Manufacturer

Type

LED

Toshiba

TLG208 (green)

TLR208 (red)

D

Rohm

1S2473

R

510 ohm 1/4W

The remote controller most
recently used (local or air
conditioner) takes precedence.

Use a remote controller with a
pulse width of 100 msec or
more.

Power On/Off cannot be controlled
from the unit’s remote controller.

When power is restored after a
power failure in this mode, On or
Off is determined according to
the current settings of the remote
controller.

Содержание Quaternity H-Series

Страница 1: ...EDUS04 906_b H Series Heat Pump...

Страница 2: ...city Tables 9 7 1 Heat Pump 9 8 Operation Limit 15 9 Sound Level 16 9 1 Measuring Location 16 9 2 Octave Band Level 17 10 Electric Characteristics 19 11 Installation Manual 20 11 1 Indoor Units 20 11...

Страница 3: ...06_b 2 Room Air Conditioners H Series 1 Power Supply Note Power Supply Intake Outdoor Unit Indoor Units Outdoor Units Power Supply Quaternity FTXG09HVJU RXG09HVJU 1 208 230V 60Hz FTXG12HVJU RXG12HVJU...

Страница 4: ...t Control Auto Fan Speed Timer Weekly Timer Indoor Unit Quiet Operation 24 Hour ON OFF Timer Night Quiet Mode Automatic Count Up down ON OFF Timer OFF only Outdoor Unit Quiet Operation Manual Night Se...

Страница 5: ...hable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 12 0 14 0 14 0 15 Power Consumption Rated W 24 26 29 31 Power Factor 87 80 7 90 1 89 9 Temperature Control Microcomputer Co...

Страница 6: ...orizontal Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 15 0 16 Power Consumption Rated W 33 35 Power Factor 95 7 95 1 Temperature Control Microcomputer Control Dimensi...

Страница 7: ...D SPACE REAR WALL HOLE LIQUID PIPE 1 4 6 4 Cut AIR PURIFYING INDIVIDUAL OPERATION SPACE FOR PERFORMANCE GEAR CASE UNIT FIXED SCREWS INSIDE PANEL INCLUDING MOUNTING PLATE LEFT SPACE FOR PERFORMANCE THE...

Страница 8: ...PRINTED CIRCUIT BOARD R1T R2T CONNECTOR OPERATION SWITCH TERMINAL STRIP SWING MOTOR M1S M4S F1U M1F H2P H3P S1 S403 CN1 FG X1M S1W THERMISTOR A1P A5P MULTI MONITOR H1P LIMIT SWITCH FOR PANEL S1C LIMI...

Страница 9: ...OOR TEMPERATURE THERMISTOR 7 9 CuT FIELD PIPING 7 9 CuT COOLING GAS STOP VALVE M MOTOR OPERATED VALVE OUTDOOR UNIT FOUR WAY VALVE ON HEATING 1 2 12 7 CuT 3 8 9 5 CuT HEAT EXCHANGER 3 8 9 5 CuT 6 4 CuT...

Страница 10: ...7 96 0 48 8 80 7 78 0 52 8 64 7 71 0 54 8 39 7 61 0 57 7 97 7 44 0 61 64 4 77 0 10 06 8 72 0 44 9 64 8 56 0 48 9 22 8 39 0 53 9 05 8 33 0 54 8 80 8 23 0 57 8 38 8 07 0 61 67 0 80 0 10 27 9 37 0 44 9 8...

Страница 11: ...e them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass...

Страница 12: ...9 01 0 82 11 18 8 86 0 85 10 62 8 62 0 92 64 4 77 0 13 41 10 15 0 67 12 85 9 92 0 73 12 29 9 69 0 79 12 07 9 60 0 82 11 73 9 46 0 86 11 17 9 24 0 92 66 9 80 1 13 69 10 80 0 67 13 13 10 57 0 73 12 57...

Страница 13: ...e them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass...

Страница 14: ...48 1 10 13 98 10 28 1 15 13 28 9 97 1 24 64 4 77 0 16 76 11 80 0 90 16 07 11 49 0 99 15 37 11 19 1 07 15 09 11 07 1 11 14 67 10 89 1 16 13 97 10 60 1 24 67 0 80 0 17 11 12 45 0 90 16 41 12 15 0 99 15...

Страница 15: ...e them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass...

Страница 16: ...nce Continuous operation 4 50 Outdoor temp FWB 68 50 68 4 FDB 68 0ft Outdoor temp FDB Air flow rate High 77 77 86 82 4 50 Cooling 5 75 32 Indoor temp FDB Indoor temp FWB 25ft 14 32 109 86 Notes 23 59...

Страница 17: ...1 Operation sound is measured in an anechoic chamber 2 The data are based on the conditions shown in the table below Indoor Unit Outdoor Unit Cooling Heating Piping Length Indoor 80 FDB 67 FWB Outdoo...

Страница 18: ...30 50 40 63 OCTAVE BAND CENTER FREQUENCY Hz 125 250 500 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL dB 0dB 0 0002 bar THRESHOLDHEARING APPROXIMATE FORCONTINUOUS NOISE POWER SOURCE JIS STANDA...

Страница 19: ...NC 60 NC 40 NC 50 NC 20 NC 30 60Hz 208 230V 49 208 230V 60Hz Cooling NC 20 NC 50 NC 60 NC 30 NC 40 48 60Hz 208 230V 208 230V 60Hz Heating 3D063011 COOLING NC 40 NC 30 NC 50 NC 60 NC 20 POWER SOURCE J...

Страница 20: ...0 15 Symbols Note MCA MIN CIRCUIT AMPS A 1 RLA is based on the following conditions Indoor temp 80 FDB 67 FWB 26 7 CDB 19 4 CWB Outdoor temp 95 FDB 35 CDB 2 Maximum allowable voltage variation between...

Страница 21: ...such as nails and other metal or wood parts including plastic packing materials used for transportation may cause injuries or death by suffocation Only qualified personnel must carry out the installa...

Страница 22: ...n be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lam...

Страница 23: ...odorizing filter for streamer 1 Remote controller holder 1 Mounting plate fixing screws 3 16 1 L M4 25mm 9 Titanium apatite photocatalytic air purifying filter 1 Dry batteries AAA LR03 alkaline 2 Fixi...

Страница 24: ...ation pipe with the finishing tape from bottom to top Install the hose with a downward slope Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left...

Страница 25: ...panel air filter and upper panel 2 Fully open the top and bottom horizontal louvers See Fig 1 3 Remove the 3 screws in the front grille 4 Lift the hooks 3 locations on the front grille with a flathead...

Страница 26: ...nd tighten with included indoor unit fixing screw 6 How to set the different addresses When 2 indoor units are installed in 1 room the 2 wireless remote controllers can be set for different addresses...

Страница 27: ...pull out if bending up the wire edge in advance 3 To connect the inter unit wiring after hooking the unit onto the mounting plate connect the inter unit wiring as shown in the figure at right A A A B...

Страница 28: ...he pipes If it is difficult to do remove the front panel first 5 Wrap the insulation on the piping with insulation tape If you are not replacing the drain hose store it in the location shown below 4 3...

Страница 29: ...necting to the HA system 6 Shape the wires so that the service lid fits securely then close service lid WARNING 1 Do not use tapped wires strand wires extension cords or starburst connections as they...

Страница 30: ...ischarge the tab 3 4 2 Pull up the electric parts box cover slowly discharge the tab 4 slide up and discharge the tab 5 5 Insert the connection cord into the HA connector S21 6 Lay the connection cord...

Страница 31: ...as a joint 8 Improving installation strength We recommend screwing the indoor unit onto a mounting plate in order to improve the installation strength 1 Remove the front grille 2 Screw in the indoor u...

Страница 32: ...serve the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030 Btu fth F 0 035 to 0 045 kcal mh C Choose heat insulation materials that are designed f...

Страница 33: ...erly on solid bases Fall vibration noise Did you install the deodorizing filter for the streamer and the titanium apatite photocatalytic air purifying filter Noise water leakage Have you performed a g...

Страница 34: ...than 10 feet 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Do not place moi...

Страница 35: ...15 16 50 More than 5 7 8 150 Top view More than 3 15 16 100 Walls facing two sides More than 1 15 16 50 More than 3 15 16 100 Side view 47 3 16 1200 or less Wall facing one side Wrap the insulation pi...

Страница 36: ...of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with the unit 4 Do never install a drier to this R410A unit in order to guarantee its...

Страница 37: ...e of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure va...

Страница 38: ...gas and liquid refrigerant pipes Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering 6 Refilling the refrigerant Check the type of refrigerant to be used on the...

Страница 39: ...he circuit by adding drain pump or other electrical equipment to unit terminals Doing so may cause electric shock or fire 3 Be sure to install an earth leak detector One that can handle higher harmoni...

Страница 40: ...tip Place the round crimp style terminals on the wires up to the covered part and secure in place Test items Incomplete cooling heating function No refrigerant gas leaks Draining line is properly ins...

Страница 41: ...eath Be sure to ventilate the room sufficiently to avoid this hazard Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other in...

Страница 42: ...as they can cut and cause injury Do not place objects in direct proximity of the outside unit Do not let leaves and other debris accumulate around the unit Leaves are a hotbed for small animals which...

Страница 43: ...t there are no obstacles close to the outside unit Obstacles close to the outside unit may drop the performance of the outside unit or increase the operating sound of the outside unit Consult your dea...

Страница 44: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 43 QUATERNITY DRYING DRY COOLING YELLOW The lamp color also changes according to the optional function...

Страница 45: ...Operation Manual EDUS04 906_b 44 Room Air Conditioners H Series Ground terminal...

Страница 46: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 45 DRY button...

Страница 47: ...Operation Manual EDUS04 906_b 46 Room Air Conditioners H Series...

Страница 48: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 47...

Страница 49: ...Operation Manual EDUS04 906_b 48 Room Air Conditioners H Series...

Страница 50: ...ries 49 DRY COOLING Operation Note on Dry Cooling operation DRY COOLING may raise humidity temporarily Hi Std Lo Constant DRY operation Note on Dry Operation The operation mode change from COOLING to...

Страница 51: ...Operation Manual EDUS04 906_b 50 Room Air Conditioners H Series...

Страница 52: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 51...

Страница 53: ...Operation Manual EDUS04 906_b 52 Room Air Conditioners H Series...

Страница 54: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 53 COOLING or DRY COOLING operation the A FLASH STEAMER AIR PURIFYING individual operation B DRY COOLING COOLING C HEATING...

Страница 55: ...Operation Manual EDUS04 906_b 54 Room Air Conditioners H Series COOLING BREEZE operation is for COOLING DRY COOLING AND FLASH STREAMER AIR PURIFYING operation...

Страница 56: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 55...

Страница 57: ...Operation Manual EDUS04 906_b 56 Room Air Conditioners H Series 1 8 F 1 C 3 6 F 2 C...

Страница 58: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 57...

Страница 59: ...Operation Manual EDUS04 906_b 58 Room Air Conditioners H Series COOLING or DRY COOLING mode or...

Страница 60: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 59...

Страница 61: ...Operation Manual EDUS04 906_b 60 Room Air Conditioners H Series...

Страница 62: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 61...

Страница 63: ...Operation Manual EDUS04 906_b 62 Room Air Conditioners H Series...

Страница 64: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 63...

Страница 65: ...Operation Manual EDUS04 906_b 64 Room Air Conditioners H Series...

Страница 66: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 65...

Страница 67: ...Operation Manual EDUS04 906_b 66 Room Air Conditioners H Series...

Страница 68: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 67...

Страница 69: ...Operation Manual EDUS04 906_b 68 Room Air Conditioners H Series...

Страница 70: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 69...

Страница 71: ...Operation Manual EDUS04 906_b 70 Room Air Conditioners H Series 3P226009 1...

Страница 72: ...pter for Time Clock Remote Control 2 Normal Open Pulse Contact Normal Open Contact KRP413A1S 3 Central Remote Controller Fahrenheit 1 DCS302C71 4 Central Remote Controller Celsius 1 DCS302CA61 5 Unifi...

Страница 73: ...d in this manual Be sure to follow instructions Be sure to perform grounding work Never attempt After installation is complete test the unit to confirm that it is working properly and instruct the own...

Страница 74: ...Indoor unit Adaptor case Install the adaptor case assy as close to the indoor unit as possible Removing case front Adaptor PCB Case front Screw Screw cover Remove the screw cover one of the screws an...

Страница 75: ...relay contacts Manufacturer Type Coil rated voltage Coil resistance Omron MY relay 12 V DC 160 ohm 10 Matsushita HC relay 12 V DC 160 ohm 10 4 Connection with Remote Controller Example connections wi...

Страница 76: ...s OFF Always Off ON Off if operation was in Off mode before power failure On if operation was in On mode before power failure Instantaneous contact Normal contact S1 1 S2 1 OPEN CLOSE S1 1 S1 2 Pulse...

Страница 77: ...re can be monitored from the Ve up controller 2 Component Parts and Separately Sold Parts which are Required This kit includes the following components Check to ensure that none of these are missing 1...

Страница 78: ...ON OFF control is rejected operate stop timer prohibition NOTE 2 During a forced stop all remote controller actions are prohibited Last command priority Contact Open to close air condition stops forc...

Страница 79: ...ed to the louver First temporarily attach the louver with 4 screws then check that the angle is correct and finally tighten the screws fully 1 Install so that a short circuit is prevented 2 For the us...

Страница 80: ...ct conforms tot he applicable standards and is suitable for use in the region where the product will be used This statement does not purport to exclude restrict or modify the application of any local...

Отзывы: