OM 1239
9
www.DaikinApplied.com
CAUTION
The MicroTech III circuit board incorporates static sensitive
devices. A static charge from touching the device can damage the
electronic components. To help prevent damage during service,
use static discharge wrist straps.Static discharge wrist straps are
grounded to the heat pump chassis through a 1 Mohm resistor.
Replacing a MicroTech III
circuit board:
1 .
Connect wrist strap to unit.
2 .
Remove faulty board and place on static protected
surface.
3 .
Remove replacement board from static protected
bag.
Note: Do not touch circuit board; hold by edges.
4 .
Holding board in grounded hand, install board in
unit.
5 .
Insert faulty board in empty static bag for return.
Initial power-up
Pre start check list:
A random start delay time between 300 and 360 seconds
is generated at power up.
Figure 5: Location of configuration jumpers on the
MicroTech III control board
Note:
Table 6 are the settings of the hardware configuration jumpers that are read when the controller is powered.
Any changes to the jumper settings require cycling power to the controller or sending a controller a reboot
command through the network communications.
Table 6: MicroTech III controller configuration jumper settings
Baseboard Description
Jumper(s)
Jumper Setting
Function
Normal / Test Mode
JP1
Open
Normal Operation
Shorted
Service / Test Mode
Fan Operation
JP2
Open
Continuous Fan Operation (On), when not operating in the unccupied mode.
Shorted
Cycling Fan Operation (Auto)
Loop Fluid
JP3
(see warning)
Open
Water Loop Fluid - Water freeze protection (factory default setting)
Shorted
Glycol Loop Fluid - Systems with anti-freeze protection
Freeze Fault Protection
JP4
Open
None
Shorted
Freeze fault protection enabled
Room Sensor Setpoint
Potentiometer Range
JP5
Open
Short Range: -5 to +5 ºF (-2.78 to +2.78 ºC)
Shorted
Long Range: 55 to 95ºF (12.78 to 35ºC)
Thermostat / Room Sensor
JP6
Open
Thermostat Control
Shorted
Room Sensor Control
Compressor Availability
JP7 & JP8
JP7 Open
Both Compressors Available (default)
JP8 Open
JP7 Shorted
One Compressor Available
JP8 Open
JP7 Open
No Compressors Available
JP8 Shorted
WARNING
Jumper JP3 is factory provided in the open position. Extended range units require freeze protection down to 15 degrees. Jumper JP3 must
be field configured.
M
ICro
t
eCh
III u
nIt
C
ontroller