Troubleshooting Guide and FAQ
OM 1085-6 • MICROTECH III CONTROLLER
Q:
The Flasher tool’s LED is red
A:
Disconnect and remove power from Flasher. After a few
seconds, reapply power to Flasher. Connect it to the unit
controller again, verifying that the triangle on the 10-pin
connector of Flasher is properly installed on the keyed
connector on the unit controller’s 10-pin JTAG port. See
Q:
After applying power, the Target VCC field changes to a
value that is too low
A:
. This could indicate a communication error
between Flasher and the unit controller. Verify that the
Flasher 10-pin connector is properly connected to the
keyed 10-pin JTAG connector port on the unit controller.
Also verify that the unit controller is connected and powered
properly. See
Figure 64:
Incorrect Target VCC Value
Q:
After preparing the file to be downloaded, the Range and/or
Target VCC fields appear in red
A:
appears, this indicates that
the device has not been properly selected. Repeat Steps
14-17 from the Flasher downloading procedure.
Figure 65: Incorrect Range and Target VCC Fields
Q:
After selecting Download and Verify, a “Busy does not
react” error message appears
A:
If the message shown in
• Verify that the Flasher5 hardware is properly connected
to the unit controller.
• Verify the programming jumper is in the “PRG” position
.
• Apply power to the unit controller and perform the
download again.
Figure 66:
Download Error Message
Q:
After selecting Download and Verify, a “supply voltage
too low” error message appears
A:
If the message shown in
power supply is properly connected to the Flasher tool and
that the power supply is plugged in to the power source.
Figure 67:
Download Error Message
Q:
After selecting Download and Verify, an “ID mismatch”
error message appears
A:
If the message shown in
following steps:
1. Verify that the passcode has been set correctly in Step
21 from the Flasher Download Procedure.
2. Remove power from the unit controller.
3. Apply power to the unit controller.
4. Repeat the Flasher download procedure.
NOTE:
Replace the unit controller if this problem persists
after repeating the programming process.