background image

Troubleshooting Guide and FAQ

www.DaikinApplied.com 35 

OM 1085-6 • MICROTECH III CONTROLLER

BACnet Communication Module Only

The following section applies only to the BACnet MS/TP 

communication module.

Light Emitting Diodes (LEDs)

The BACnet communication module has four LEDs that 

indicate the status of the module, the connection to the unit 

controller and/or BACnet network. These LEDs are useful for 

verifying communication between the unit controller and the 

network, as well as diagnosing a potential problem. 

Table 17

 

provides a description of the LED activity. For more details, see 

IM 928

, available on 

www.DaikinApplied.com

.

Table 17: BACnet Communication Module - LED Activity

LED

Function

Description

D1

Program Running

Program main loop activity

D2

Unit Controller Message SPI Activity, LED on during unit controller 

message

D3

MS/TP Transmit

Flashes on when transmitting a MS/TP 

message

D4

MS/TP Receive

Flashes on when receiving a MS/TP 

message

Q:

 No LEDs are lit

A:

 The communication module may not be properly installed or 

may not have the BACnet application software loaded.

•  Remove the communication module and then reinstall 

it, verifying that the connector lands on all of the pins (it 

is very easy to either miss just one pin or all of the pins 

even with the standoffs).

•  If the communication module is properly installed, try it 

on a different, functioning unit. If the LEDs still do not 

function properly, replace the communication module.

•  Re-download the BACnet software in the communication 

module. 

Contact the Controls Customer Support 

group at 866-462-7829 before proceeding with this 

option .

Q:

 All four LEDs are lit

A:

 The BACnet application software has not been properly 

downloaded.

•  Re-download the BACnet software in the communication 

module.

•  Replace the BACnet communication module.

Q:

 Program LED (D1) never blinks

A:

 The BACnet software is not running correctly in the 

communication module.

•  Re-download the BACnet software in the communication 

module.

•  Replace the BACnet communication module.

Q:

 SPI Comm LED (D2) never blinks

A:

 The communication module is not communicating with the 

unit controller.

•  Verify that the programming jumper on the baseboard is 

in the RUN position and not the PRG position.

•  Verify that unit controller is controlling the water source 

heat pump unit.

•  Re-download the unit controller application code.
•  Re-download the BACnet software in the communication 

module.

• 

Install the communication module on a different, 

functioning unit to determine if the problem is associated 

with the unit controller or the communication module.

Q:

 RX LED (D4) never blinks

A:

 The communication module is not communicating with the 

network.

•  Verify the BACnet MS/TP settings through the serial port 

on the communication module (check baud rate and any 

potential addressing conflicts).

•  Verify proper network wiring.
•  Re-download the BACnet software in the communication 

module.

•  If the network settings are correct and the application 

software is functioning properly, this could indicate a 

hardware defect. Replace the communication module, if 

necessary.

Q:

 CRC errors

A:

 The BAS indicates “CRC errors” at the workstation.

•  Upgrade the communication module to the newest 

version of BACnet software. It is not necessary to 

upgrade the unit controller or I/O expansion module 

software.

Q:

 Communication module cannot be configured through 

serial port

A:

 This could be caused by an incorrect or defective cable 

used to configure the communication module, software 

installation error, a previous change in the serial port 

settings, or potentially defective hardware.

•  Verify that the communication module is connected with 

a DB9 female-female (modem-modem) serial cross-over 

cable. Refer to the MicroTech III WSHP Unit Controller 

Protocol Document, 

ED 15103

, available on 

www.

DaikinApplied.com

.

• 

Confirm that the serial terminal device application settings 

are correct. . Refer to the MicroTech III WSHP Unit 

Controller Protocol Document, 

ED 15103

, available on 

www.DaikinApplied.com

•  Verify that the LED activity is normal. See 

Table 17

.

•  Try resetting the communication module back to original 

default settings.

•  Re-download the BACnet software in the communication 

module. 

•  Replace the communication module, if necessary.

Содержание MicroTech III

Страница 1: ...Tech III Water Source Heat Pumps WSHP Unit Controller I O Expansion Module BACnet and LonWorks Communication Modules Models GSH GSV GTH GTV GCV SmartSource Single and Two Stage Compressor CCH CCW LVC...

Страница 2: ...with Segger Flasher5 Programmer 15 Download and Configuration BACnet 19 BACnet Communication Module 19 Downloading Segger J Flash ARM Software and J Link Hardware 19 Download and Configuration LonWor...

Страница 3: ...oller Operation and Maintenance Manual www DaikinApplied com OM 1149 MicroTech III Water Source Heat Pump SmartSource Single Two Stage Compressor Series2 Unit Controller Operation and Maintenance Manu...

Страница 4: ...dules in addition to the baseboard I O Expansion Module Optional daughter board that provides additional input output capability for secondary compressor multiple speed fan secondary heating and dehum...

Страница 5: ...Yes Yes Yes Yes Yes4 Yes4 Yes4 v2 82 Yes Yes Yes Yes Yes Yes Yes4 Yes4 Yes4 v3 02 Yes Yes Yes Yes Yes Yes Yes4 Yes4 Yes4 v3 1 Yes Yes Yes Yes Yes Yes Yes Yes Yes 1 BACnet software v3 4 or greater is r...

Страница 6: ...2 LonWorks software v1 1 or greater is recommended for optimal network communications performance Table 4 Software Compatibility Enfinity Two Speed Compressor Multi Fan Speed Series1 Models WSHP Unit...

Страница 7: ...Renesas Flash Development Toolkit software available at www renesas com us en products software tools tools programmer flash development toolkit programming gui html Unit controller software which is...

Страница 8: ...differences are noted where necessary 1 Acquire the Renesas E2 Lite programmer and interface cable as described in Table 5 2 Download the latest Renesas Flash Programmer RFP software from the Renesas...

Страница 9: ...rface cable from the CN_PGRM port of the baseboard or IO expansion board 15 Close the RFP software Programming is now complete and the board is ready for use Figure 4 Renesas E2 Lite Programmer USB Co...

Страница 10: ...d com Download and Configuration Figure 8 Renesas Programmer Attached to the 6 pin Connection Port of Interface Ribbon Cable Figure 9 Programming Hardware Fully Connected Note the red strip on the rib...

Страница 11: ...e mini plug of the USB interface cable to the USB I F connector of the E8a b Connect the plug of the USB interface cable to the USB port on your computer NOTE The E8a programmer is active once connect...

Страница 12: ...Figure 13 11 Select 740 M38507F8A and click Next Figure 13 Select Device From the Communications Port screen Figure 14 12 Select E8a from the Select Port drop down menu 13 Check Set Reset pin as low w...

Страница 13: ...r Properties Settings Target Power 25 Click Memorize the settings in this dialog box until the work space is closed and then click OK Figure 19 Figure 19 Target Power Settings In the File Selection ar...

Страница 14: ...es appear in the status area at the bottom of the screen 31 Verify the Image Written to Device and Verification OK messages are displayed These messages indicate a successful download 32 Close the Ren...

Страница 15: ...s of JTAG supported programming tools that would also be acceptable Figure 22 Choose Destination Figure 23 Choose Options Once the Flasher software has been installed follow the steps below to downloa...

Страница 16: ...gate to the Control Panel and select System Hardware Device Manager Ports 13 Verify the communication port shown i e COM1 COM2 etc 14 Launch the Flasher program from the desktop shortcut icon 15 If th...

Страница 17: ...he software file for downloading a Go to the File menu and select Open b Browse to the appropriate file and click OK The screen should populate as indicated in Figure 31 25 To begin the download selec...

Страница 18: ...operating parameters a Place the unit in the Service Mode by shorting the unit controller JP1 configuration jumper b Tie a jumper wire from a ground connection to the unit controller unoccupied input...

Страница 19: ...on module software Getting Started You will need the following BACnet communication module hardware PN 668105901 installed on the WSHP unit controller The latest Segger J Link hardware J Link Plus bun...

Страница 20: ...tion module Figure 33 2 Launch J Flash ARM software The screen shown in Figure 35 appears Figure 35 J Flash ARM Initial Project Screen Configure J Link Hardware Follow the below to establish the prope...

Страница 21: ...Device Selection 10 Verify that Device is now set to Atmel AT91SAM7S256 Figure 40 11 Verify 200000 is in the Addr box and 64KB is selected from the drop down menu then click Apply Figure 40 MCU Tab V...

Страница 22: ...o button is selected 25 Click OK to exit the Global Settings menu Figure 44 Global Settings Downloading BACnet Communication Module Software with J Flash ARM CAUTION The following procedure returns al...

Страница 23: ...eset push buttons on the BACnet communication module as shown in Figure 33 16 Apply power to the unit controller 17 Release the Reset push button and continue to hold the Default push button until all...

Страница 24: ...ystem Refer to www echelon com for details Standard web browser for access to www DaikinApplied com Installation and Setup 1 Verify that LonWorks software such as LonMaker SR4 or CT is installed 2 Ver...

Страница 25: ...network i Select the network from the Drawing directory drop down menu ii Click on Open Network iii Proceed to the Commissioning the LonWorks Communication Module section b To create a new network i...

Страница 26: ...e appears in yellow indicating the device is decommissioned Figure 56 Network Drawing Commissioning the LonWorks Communication Module The LonWorks communication module is ready for network commissioni...

Страница 27: ...rvice pin button on the LonWorks communication module Refer to Figure 49 for the location of the service button Figure 60 Service Pin Entry At this point the application image starts loading the LonWo...

Страница 28: ...ted Service Test Mode Fan Operation JP2 JP2 Open Continuous Fan Operation ON JP2 Shorted Cycling Fan Operation AUTO Loop Fluid JP3 JP3 Open Water Loop Fluid JP3 Shorted Glycol Loop Fluid Alarm A Termi...

Страница 29: ...rce Compact Table 8 Unit Controller Configuration Jumpers for SmartSource Single and Two Stage Compressor Series2 and SmartSource Compact Unit Controller Option Hardware Jumpers Setting Description No...

Страница 30: ...horted Dual Stage Compressor Table 10 Model Types and Options for SmartSource Single and Two Stage Compressor Series2 and SmartSource Compact3 Model Number Compressor Type Supplemental Electric Heat B...

Страница 31: ...d Compressor Available Lag Compressor is Off Line JP8 Open JP7 Open No Compressors Available JP8 Shorted Table 12 I O Expansion Module Configuration Jumpers for Enfinity Large Two Compressor SS2C I O...

Страница 32: ...JP8 JP7 Open Single Speed Fan JP8 Open JP7 Shorted Two Speed Fan User Selectable JP8 Open JP7 Open Three Speed Fan Automatic JP8 Shorted 1JP2 setting applies only if 1 there is a room sensor and 2 th...

Страница 33: ...e X X 5 One One X X 6 One One X X X 7 One One X X X 8 One One X 9 One One X X 10 One One X X 11 One One X X 12 One One X X 13 One One X X X 14 One One X X X 15 One One X X 16 One One X X X 17 One One...

Страница 34: ...ition in the Enfinity Single Stage Compressor software that creates nuisance high pressure alarms This condition is seen approximately once every 1000 compressor cycles d For Enfinity Single Stage Com...

Страница 35: ...module Q SPI Comm LED D2 never blinks A The communication module is not communicating with the unit controller Verify that the programming jumper on the baseboard is in the RUN position and not the P...

Страница 36: ...and then re install it making sure the connector snaps into place on all four of the pins Use caution as it is easy to either miss just one pin or all of the pins even with the standoffs Verify if the...

Страница 37: ...rly selected Repeat Steps 14 17 from the Flasher downloading procedure Figure 65 Incorrect Range and Target VCC Fields Q After selecting Download and Verify a Busy does not react error message appears...

Страница 38: ...the Download BACnet Communication Module Software section 5 Remove the jumper from pin 4 and pin 5 on J2 of the BACnet communication module if connected Figure 72 6 With power applied to the unit cont...

Страница 39: ......

Страница 40: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representativ...

Отзывы: