IM 971-3 • MAVERICK I 60 www.DaikinApplied.com
Performance Data
Figure 40:
Airflow Performance – MPS 008D
Air
Flow
CFM
[L/s]
Model MPS 008D
External Static Pressure—Inches of Water [kPa]
0 .1 [ .02] 0 .2 [ .05] 0 .3 [ .07] 0 .4 [ .10] 0 .5 [ .12] 0 .6 [ .15] 0 .7 [ .17] 0 .8 [ .20] 0 .9 [ .22] 1 .0 [ .25] 1 .1 [ .27] 1 .2 [ .30] 1 .3 [ .32] 1 .4 [ .35] 1 .5 [ .37] 1 .6 [ .40] 1 .7 [ .42] 1 .8 [ .45] 1 .9 [ .47] 2 .0 [ .50]
RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W
2700
[1274]
—
— 561 894 596 934 631 975 665 1018 698 1062 730 1108 762 1155 793 1203 823 1253 853 1304 882 1357 910 1411 937 1467 964 1524 990 1583 1015 1643 1039 1704 1063 1767 1086 1832
2800
[1321]
—
— 573 927 608 969 642 1013 676 1058 708 1104 740 1152 771 1201 802 1252 832 1304 861 1358 889 1413 917 1470 943 1528 970 1587 995 1648 1020 1711 1044 1775 1067 1840 1090 1907
2900
[1368]
—
— 586 964 620 1008 654 1054 687 1101 719 1150 750 1200 781 1252 811 1305 840 1360 869 1416 897 1473 924 1532 950 1593 976 1654 1001 1718 1025 1782 1048 1848 1071 1916 1093 1985
3000
[1416]
564 959 599 1004 633 1051 666 1099 698 1149 730 1200 761 1253 791 1307 820 1362 849 1419 877 1477 904 1537 931 1598 957 1661 982 1725 1006 1791 1030 1858 1053 1926 1075 1996 1097 2067
3100
[1463]
578 1001 612 1048 645 1098 678 1148 710 1200 741 1254 771 1308 801 1365 830 1423 858 1482 886 1542 912 1605 939 1668 964 1733 989 1800 1012 1868 1036 1937 1058 2008 1080 2080 1101 2154
3200
[1510]
592 1046 625 1096 658 1148 690 1201 721 1255 752 1311 782 1368 811 1427 840 1487 867 1548 894 1611 921 1676 946 1742 971 1809 995 1878 1019 1948 1041 2020 1063 2093 1085 2168 1105 2244
3300
[1557]
605 1096 638 1148 671 1202 702 1257 733 1314 763 1372 793 1432 821 1493 849 1555 877 1619 903 1684 929 1751 954 1819 979 1889 1002 1960 1025 2033 1047 2107 1069 2182 1090 2259 1110 2337
3400
[1604]
619 1149 652 1204 684 1260 715 1317 745 1376 775 1437 804 1499 832 1562 860 1627 886 1693 912 1761 938 1830 962 1900 986 1972 1009 2046 1032 2121 1053 2197 1074 2275 1095 2354 1114 2435
3500
[1652]
634 1206 666 1263 697 1322 728 1382 758 1443 787 1506 815 1570 843 1635 870 1702 896 1771 922 1841 946 1912 970 1985 994 2060 1017 2135 1038 2213 1060 2291 1080 2371 1100 2453 1119 2536
3600
[1699]
648 1267 680 1326 711 1387 741 1449 770 1513 799 1578 827 1645 854 1713 880 1782 906 1853 931 1925 955 1999 979 2074 1002 2151 1024 2229 1045 2308 1066 2389 1086 2472 1105 2556 1124 2641
3700
[1746]
663 1332 694 1393 724 1456 754 1521 783 1587 811 1654 838 1723 865 1793 891 1865 916 1938 941 2013 965 2089 988 2167 1010 2246 1032 2326 1053 2408 1073 2491 1092 2576 1111 2662 1129 2750
3800
[1793]
678 1400 708 1464 738 1529 767 1596 795 1665 823 1734 850 1805 876 1878 902 1952 926 2028 951 2105 974 2183 996 2263 1018 2344 1039 2427 1060 2511 1080 2597 1099 2684 1117 2772 1134 2862
3900
[1840]
693 1472 723 1538 752 1606 781 1675 808 1746 836 1818 862 1892 888 1966 913 2043 937 2121 961 2200 983 2281 1005 2363 1027 2447 1048 2532 1067 2618 1087 2706 1105 2796 1123 2886 1140 2979
4000
[1888]
708 1548 737 1617 766 1687 794 1758 822 1831 848 1906 874 1981 900 2059 924 2137 948 2218 971 2299 993 2382 1015 2467 1036 2553 1056 2640 1075 2729 1094 2819 1112 2911 1129 3004 1146 3099
4100
[1935]
723 1628 752 1699 781 1771 808 1845 835 1920 861 1997 887 2075 911 2155 935 2236 959 2318 981 2402 1003 2488 1024 2574 1045 2663 1064 2752 1083 2844 1101 2936 1119 3030 1136 3126 1152 3223
NOTE
: A/F-Drive left of 1st bold line, B/G-Drive in middle of bold lines, C/H-Drive right of 2nd bold line.
Drive Package
A/F
B/G
C/H
Motor H .P . [W]
2.0 [1491.4]
3.0 [2237.1]
3.0 [2237.1]
Blower Sheave
AK79H
AK79H
AK79H
Motor Sheave
1VL40*7/8
1VP50*7/8
1VP56*7/8
Turns Open
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
RPM
804
758
710
661
616
559 1048 1003 959
914
872
826
1168 1128 1087 1044 1002 957
NOTES:
1. Factory sheave settings are shown in bold type.
2. Do not set motor sheave below minimum or maximum turns open shown.
3. Re-adjustment of sheave required to achieve rated airflow at AHRI minimum External Static Pressure
4. Add component resistance (below) to duct resistance to determine total External Static Pressure.
Airflow Correction Factors – 8.5 Ton [29.9 kW]
Actual
CFM
[L/s]
2700
[1274]
2900
[1368]
3100
[1463]
3300
[1557]
3500
[1652]
3700
[1746]
3900
[1840]
4100
[1935]
Total
MBH
0.97
0.98
0.99
1.01
1.02
1.03
1.04
1.05
Sensible
MBH
0.93
0.96
0.99
1.01
1.04
1.07
1.10
1.13
Power
kW
0.99
0.99
1.00
1.00
1.01
1.02
1.02
1.03
NOTES:
[ ] Designates Metric Conversions
1. Multiply correction factor times gross performance data.
2. Resulting sensible capacity cannot exceed total capacity.
3. Add component resistance to duct resistance to
determine total external static pressure.
4. DNA = Data not Available.
Component Air Resistance, IWC – 8 .5 Ton [29 .9 kW]
Component
2700
[1274]
2900
[1368]
3100
[1463]
3300
[1557]
3500
[1652]
3700
[1746]
3900
[1840]
4100
[1935]
Resistance – Inches Water [kPa]
Wet Coil
0.07
[0.02]
0.08
[0.02]
0.09
[0.02]
0.10
[0.03]
0.11
[0.03]
0.13
[0.03]
0.14
[0.04]
0.15
[0.04]
Vertical
Economizer
100% R.A.
Damper Open
0.03
[0.01]
0.04
[0.01]
0.06
[0.01]
0.08
[0.02]
0.10
[0.02]
0.12
[0.03]
0.15
[0.04]
0.17
[0.04]