![Daikin Maverick I MPSA07D Скачать руководство пользователя страница 12](http://html2.mh-extra.com/html/daikin/maverick-i-mpsa07d/maverick-i-mpsa07d_installation-and-maintenance-manual_5693281012.webp)
IM 971-3 • MAVERICK I 12 www.DaikinApplied.com
Mechanical Installation
Table 7: Meter Time in Minutes and Seconds for Normal Input Rating of Furnaces Using Natural or LP Gas
Input
Btu/ hr
Meter Size
Cu .Ft .
Heating Value of Gas Btu Per Cu .Ft .
LP (cu . Ft .)
900
1000
1050
1100
2500
Minutes
Seconds
Minutes
Seconds
Minutes
Seconds
Minutes
Seconds
Minutes
Seconds
150,000
One
0
22
0
24
0
25
0
26
1
0
Ten
3
36
4
0
1
16
4
24
10
0
205,000
One
0
16
0
18
0
18
0
19
0
44
Ten
2
38
2
56
0
55
3
13
7
19
225,000
One
0
14
0
16
0
17
0
18
0
40
Ten
2
24
2
40
0
50
2
56
6
40
Table 8: LP Gas Pipe Capacity (Cubic feet per hour)
Nominal
Iron Pipe
Size, Inches
Length of Pipe, Feet
10
20
30
40
50
60
70
80
90
100
½
275
189
152
129
114
103
96
89
83
78
¾
567
393
315
267
237
217
196
182
173
162
1
1,071
732
590
504
448
409
378
346
322
307
1¼
2,205
1,496
1,212
1039
913
834
771
724
677
630
1½
3,307
2,299
1,858
1,559
1,417
1,275
1,181
1,086
1,023
976
2
6,221
4,331
3,465
2,992
2,646
2,394
2,205
2,047
1,921
1,811
Start the furnace and measure the time required to burn one
cubic foot of gas. Prior to checking the furnace input, make
certain that all other gas units are shut OFF, with the exception
of pilot burners. Time the meter with only the furnace in
operation.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET
(610 METERS):
The main burner orifices in your furnace and
in these kits are sized for the nameplate input and intended
for installations at elevations up to 2,000 feet in the USA or
Canada, or for elevations of 2,000 - 4,500 feet (610 1,373
meters) in Canada if the unit has been derated at the factory.
For elevations above 2,000 feet (610 meters)
IN THE USA
ONLY
(see ANSIZ223.1), the burner orifices must be sized to
reduce the input 4% for each 1,000 feet (305 meters) above
sea level.
NOTICE:
Derating of the heating input for high altitude in the
field is unlawful in Canada (refer to CAN/CGA 2.17). Units
installed in altitudes greater than 2,000 feet (610 meters)
must be shipped from the factory or from a factory authorized
conversion station with the heating input derated by 10% so
as to operate properly in altitudes from 2,000 - 4,500 feet (610
1,373 meters).
Condensate Drain
The condensate drain connection of the evaporator is threaded
¾" nominal iron pipe.
IMPORTANT:
Install a condensate trap
to ensure proper condensate drainage. See
Figure 11: Condensate Drain
Содержание Maverick I MPSA07D
Страница 82: ...IM 971 3 MAVERICK I 82 www DaikinApplied com Maintenance Figure 56 System Charging Charts 8 5 Ton Two Stage AC...
Страница 83: ...Maintenance www DaikinApplied com 83 IM 971 3 MAVERICK I Figure 57 System Charging Charts 10 Ton Two Stage AC...
Страница 84: ...IM 971 3 MAVERICK I 84 www DaikinApplied com Maintenance Figure 58 System Charging Charts 12 5 Ton AC...
Страница 93: ......