IM 971-3 • MAVERICK I
6 www.DaikinApplied.com
Mechanical Installation
Clearances
The following minimum clearances must be observed for
proper unit performance and serviceability (also see
Figure 3: Clearances
Table 2: Recommended Clearances
Recommended Clearance In . [mm]
Location
48 [1219]
A - Front
24 [609]
B - Condenser End
48 [1219]
1
C - Duct End
24 [609]
2
D - Filter Side
60 [1524]
E - Above
1. 18" [457 mm] Minimum if drain pan will not be removed.
2. 48" [1219 Mm] Minimum if economizer is installed.
Rooftop Installation
1. Before locating the unit on the roof, make sure that the
roof structure is adequate to support the weight involved.
(See Electrical & Physical Tables in this manual.)
THIS IS VERY IMPORTANT AND THE INSTALLER’S
RESPONSIBILITY .
2. For rigging and roofcurb details, see
.
3. The location of the unit on the roof should be such as to
provide proper access for inspection and servicing.
IMPORTANT:
If unit will not be put into service immediately,
block off supply and return air openings to prevent excessive
condensation.
Figure 4: Flat Rooftop Installation, With Attic or Drop
Ceiling Distributing System
VERTICAL
CLEARANCE
A
B
D
C
E