IM 971-3 • MAVERICK I 14 www.DaikinApplied.com
Electrical Installation
Figure 13: Base Entry Locations
Table 10:
Recommended Wire Sizes
Wire Size,
AWG
14
12
10
8
6
4
3
2
1
0
00
000
Conduit Size
1/2"
1/2"
1/2"
3/4"
1"
1"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
2"
2"
Hole Size
7/8"
7/8"
7/8"
1-31/32"
1-23/64"
1-23/64"
1-23/32"
1-23/32"
1-31/32"
1-31/32"
2-15/32"
2-15/32"
Hook-Up
To wire unit, refer to the following hook-up diagram. Refer to
entrances. Wiring to be done in the field between the unit and
devices not attached to the unit, or between separate devices
which are field installed and located, shall conform with the
temperature limitation for Type T wire [63°F rise (35°C)] when
installed in accordance with the manufacturer’s instructions.
Internal Wiring
A diagram of the internal wiring of this unit is located on the
inside of control access panel and in this manual. If any of the
original wire as supplied with the unit must be replaced, the
wire gauge and insulation must be same as original wiring.
208 Volt Applications
Transformer is factory wired for 230 volts on 208/230 volt
models and must be changed for 208 volt applications. See
unit wiring diagram for 208 volt wiring.
WIRE SIZE FROM
MIN. CIRCUIT AMPACITY
WIRE FROM
ZONE THERMOSTAT
CONDUIT FROM
POWER SUPPLY
SIZED PER CHART
STRAIGHT CONDUIT
FITTING SIZED
PER CHART
CONDUIT FROM
ZONE THERMOSTAT
STRAIGHT
CONDUIT FITTING
POWER ENTRY
CUT HOLE
SIZED PER CHART
CONTROL VOLTAGE
CUT HOLE PER CHART
CONDUIT
NUT
MAIN
GAS VALVE
EXTERNAL
PIPING
SUPPLIED
BY OTHERS
EXTERNAL
GAS VALVE
BOTTOM
GAS ENTRY