3-5
3.3 Automatic PTI
●
Automatic PTI enable condition
43
℃
≧
Ambient temperature
≧
-10.0
℃
Ambient temperature above 43
℃
or below -10.0
℃
may result in PTI failure.
●
Four options for automatic PTI are available, Short PTI, Full PTI, Chilled PTI and Frozen PTI.
PTI
Content
Short PTI
Performed in order to find parts abnormalities. PTI continues even if abnormalities are
found during PTI. But it terminates as soon as the compressor failure or the evaporator
fan lock is detected.
Full PTI
Short PTI, Chilled PTI and Frozen PTI are performed.
It terminates as soon as abnormalities are found after the completion of Short PTI
Chilled PTI
Short PTI and Chilled PTI are performed.
It terminates as soon as abnormalities are found after the completion of Short PTI
Frozen PTI
Short PTI and Frozen PTI are performed.
It terminates as soon as abnormalities are found after the completion of Short PTI
●
Access
1. Press MENU key at preparation display after I/O switch ON, and go to
"Initialize Menu".
2. Select "PTI Menu" and press
key in the "Initial Menu", and go to "PTI
Menu".
3. Move cursor to select PTI and press
key, then the PTI will start.
4. Press I/O switch OFF when the PTI is completed.
※
Pass for completion of PTI operation for failure is displayed
PTI
Pass
Full PTI
Pass
PTI
Fault
Full PTI
1/1
T221 HSV malfunction
T101 HPS cut OFF
HPS cut OFF
Preparation for 10 sec.
ON
[ Initialize Menu ]
PTI Menu
Full PTI
Chilled PTI
Frozen PTI
Short PTI
[ PTI Menu ]
Manual Check
Config Set
Optional Function
PTI Menu
USB Menu
Initialize Menu
Switch OFF
Switch OFF
UNIT OFF
System Check
10
Container ID DILU1234567
Controller Date DD/MM/ YYYY
Controller Time 17:00
SoftWare Ver. 25E1