2-20
●
E Alarm
Diagnosis
Alarm
code
Alarm content
Controller action
001
E101
HPS activates during operation
Restart after 3 min.
101
E105
Compressor over current at startup (>51A)
Restart after 3 min.
011
E107
DCHS1 or DCHS2 becomes 130
℃
or more for 10 minutes or 145
℃
or more.
Restart after 3 min.
002
E109
LPT remains at -70kPa or lower during operation
Restart after 3 min.
010
E115
Condenser fan motor internal thermostat activated
Restart after 3 min.
011
E201
Pumpdown is not completed in rated time.
Alarm display only
013
E202
Automatic pumpdown failure
Alarm display only
014
E203
Overcooling Protection
Restart after 3 min.
014
E207
Defrost is not completed in 90 min.
Alarm display only
003
E303
Humidity setting requirement (during dehumidification operation)
Alarm display only
015
E304
Reheat Coil Setting Error
Alarm display only
003
E305
Defrost interval setting requirement
Alarm display only
003
E307
Calendar setting requirement
Alarm display only
003
E311
Trip start setting requirement
Alarm display only
016
E401
Supply air temperature sensor (SS) failure
Backup operation
016
E402
Data recorder supply air temperature sensor (DSS) failure
Backup operation
016
E403
Return air temperature sensor (RS) failure
Backup operation
016
E404
Data recorder return air temperature sensor (DRS) failure
Backup operation
017
E405
Discharge gas temperature sensor (DCHS1) failure
Backup operation
018
E406
Suction gas temperature sensor (SGS) failure
Backup operation
018
E407
Evaporator inlet temperature sensor (EIS) failure
Backup operation
018
E409
Evaporator outlet temperature sensor (EOS) failure
Backup operation
018
E411
Ambient temperature sensor (AMBS) failure
Alarm display only
019
E413
Low pressure transducer (LPT) failure
Backup operation
019
E415
High pressure transducer (HPT) failure
Backup operation
020
E417
Power voltage sensor (PT) failure
Alarm display only
021
E419
Current sensor (CT) failure
Alarm display only
022
E425
USDA #1 sensor failure
Alarm display only
022
E427
USDA #2 sensor failure
Alarm display only
022
E429
USDA #3 sensor failure
Alarm display only
023
E431
Humidity sensor (HuS) failure
Alarm display only
022
E433
Cargo temperature sensor (CTS) failure
Alarm display only
018
E435
Economizer inlet temperature sensor (ECIS) failure
Backup operation
018
E437
Economizer outlet temperature sensor (ECOS) failure
Backup operation
017
E439
Discharge gas temperature sensor (DCHS2) failure
Backup operation
024
E607
Sheet key fault (Status of the key being kept pressed lasted at
least one minute.)
Alarm display only
005
E701
Abnormal power voltage is detected during operation.
(
≧
530V or
≦
300V)
Restart after 3 min.
One of R, S or T phase missing during operation
025
E707
Instantaneous power shut down during operation
Restart after 3 min.
026
E801
Back-up battery failure
Alarm display only
027
E805
Ventilator opening FA sensor failure
Alarm display only
028
E807
Ventilator FA opens during frozen operation
Alarm display only
009
E809
Refrigerant shortage
Restart after 3 min.
029
E903
Communication error between CPU board and operation board
Alarm display only