2-44
108
E533
Alarm
Logic
①
Power supply remains in
≧
530V or
≦
300V.
②
One of phase is missing in power supply to inverter.
Possible
Causes
①
Power voltage remains more than upper limit (
≧
530V) or lower than lower limit (
≦
300V).
②
Check if there is broken wire (open) or phase missing in the power supply to inverter
(secondary side of circuit breaker).
Trouble
Shooting
①
Power supply check
Check if the power supply voltage is within
allowable range
(
300V
〜
530V).
②
Check if there is broken wire (open) in the
secondary side of circuit breaker.
*
Between C/B
〜
X205A
(
inverter board
)
①
Provide the power supply voltage within
allowable range.
Electrical parts may have damages.
②
Repair if there is broken wire in the
secondary side of circuit breaker.
*
Between C/B
〜
X205A
(
inverter board
)
Controller
Action
E533
Restart after 3 minutes standby (Permanent retry
)
109
E542
Alarm
Logic
Fan motor for cooling is faulty
Possible
Causes
①
Fan motor for cooling is lock or faulty cable connection
②
Inverter failure (detection part of motor lock
)
Trouble
Shooting
①
Check if fan motor for cooling is lock or faulty cable connection (disconnection or short circuit)
②
If there is no fault in motor and cable, it seems to be inverter board failure.
Replace inverter board.
Controller
Action
E532
Alarm display only
110
Communication Interrupted
(
E5FF
)
Alarm
Logic
E5FF: Communication error between CPU board and inverter board during operation
Possible
Causes
①
Cable fault or connection error between inverter board and CPU board
②
Inverter board failure (Communication part to CPU board)
③
CPU board failure (Communication part to inverter board)
Trouble
Shooting
①
Disconnect the connector of cable between CPU board
(
connector X19A
)
and inverter board
(
connector X4A
)
and check pins visually.
Insert socket sucurely after checking of cable disconnection or short circuit.
②
If there is no connection error between both boards, it seems to be inverter board or CPU
board failure.
Controller
Action
Communication Interrupted
(
E5FF
)
Restart after 3 minutes standby (permanent retry
)
(
"Communication Interrupted" is indicated on LCD and the E903 event log is recorded.)