Troubleshooting
SiENBE28-901
88
Air Cooled Refrigeration Condensing Unit
6.6.3 “
E3
” Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
The protection device circuit checks continuity in the high pressure switch.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 3.8MPa
Reset pressure:
2.85MPa
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of high pressure switch
Defect of outdoor unit main PCB (A1P)
Instantaneous power failure
Faulty high pressure sensor