SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
73
6. Troubleshooting
6.1
Checking Points at Servicing
Symptoms and check points
The following symptoms are not malfunctions
Symptoms
Check points
Countermeasure and check details
Temperature
inside the
showcase is at
abnormal level.
Is the outdoor unit running?
Check the operation switch, signal line
R1·R2 and malfunction display.
Is the sight glass liquid-sealed (in
cooling)?
Charge refrigerant.
Is the showcase's fan running?
Check the disconnection, and
malfunction. (in the showcase)
Is the showcase's solenoid valve
operating properly?
Rectify the solenoid valve.
Is the showcase's thermostatic
expansion valve operating properly?
(No broken capillaries?)
Check the state of mounting the body
and feeler bulb.
Is the defrost operation conducted
properly? (No excessive frosting?)
Actuate the forced defrosting. Check the
defrosting cycle and the disconnection
in the heater.
Is the outdoor unit heat exchanger
blocked with dust or the like?
Clean the heat exchanger.
Is the air curtain blocked at the air outlet
or inlet of showcase?
Remove the obstacles.
Equipment does
not run.
Check to be sure the malfunction code
on the remote controller.
Countermeasure to the malfunction
code.
Check to be sure the malfunction LED
display on the outdoor unit PCB.
Countermeasure to the malfunction LED
display.
Symptoms
Causes
Equipment does
not operate.
When the equipment is restart
immediately after it stops.
The equipment is controlled in an
affordable way.
The equipment will automatically start
running after a lapse of 1 to 5 min.
Immediately after power supply in
turned ON.
The equipment is kept in standby mode
until the micro-computer gets ready for
operation. Wait for a period of approx. 2
min.
Sounds are
produced.
(Outdoor unit)
A faint continuous hissing sound
produced while in refrigerating
operation.
This is a sound produced when gas
(refrigerant) flows to the outdoor unit.
(Outdoor unit)
A faint continuous hissing sound
produced immediately after startup or
stop of the unit.
This is a sound when gas (refrigerant)
stops flowing or the flow is changed.
(Outdoor unit)
An operating sound changes in the tone
interval.
This sound is produced through
changing the compressor operating
frequency.
The outdoor unit
fan does not
run.
While in operation.
The fan speed is controlled in order to
put the equipment into optimum
operating conditions.