Troubleshooting
SiENBE28-901
74
Air Cooled Refrigeration Condensing Unit
1. Guideline for right operating conditions.
Operating conditions: outdoor temp.: 32°CD.B.
Note that the values shown above may vary significantly, depending on the environment in
which the unit is being used.
2. Emergency operation in the case of a compressor with poor electrical insulation
(This only applies to a system with multiple compressors.)
Usually, if a compressor stops because of a problem, the system will automatically perform a
backup operation (i.e., emergency operation) using other, properly-functioning compressors.
However, if the source breaker trips due to poor electrical insulation of a compressor, the
whole system will shut down and no backup operation will be possible.
If this happens, you need to run the other working compressors using the following
procedures.
2-1. Procedure of emergency operation
Operating the main circuit breaker twice makes it possible to conduct the forced backup
operation. (i.e., to prohibit the operation of compressors having a failure in insulation
and only to forcedly run operable compressors.)
(Procedures)
1. Set the main circuit breaker of the outdoor unit to ON.
2. Set the main circuit breaker to ON again.
(The forced backup operation will be initiated.)
Precautions:
Item
Measuring method
Right range
High pressure
(MPa)
Measure with a service checker or
pressure gauge in a stable state 20
minutes or more after starting
operation.
2.1 - 2.7 MPa
Low pressure
(MPa)
Measure with a service checker or
pressure gauge in a stable state 20
minutes or more after starting
operation.
0.0 MPa to target LPm + 0.05 MPa
Discharge pipe
temperature
(°C)
Measure the temperature using a
surface thermometer or service checker.
(Tc + 10) to 120°C
Tc: high pressure equivalent saturation
temperature
Suction pipe
temperature
(°C)
Measure the temperature using a
surface thermometer or service checker.
(Te + 10) to 50°C
Te: low pressure equivalent saturation
temperature
Restarting operation will make automatic judgement
on the insulation conditions of parts concerned
again.
↓
"Malfunction judgement":
The main circuit breaker will be set to OFF again.
→
"Normal judgement":
The operation will be
continued.
The timing to turn OFF the circuit breaker varies with faulty parts.
If the INV compressor has a failure in insulation, the circuit breaker will be immediately
activated. However, if the STD compressor has a failure in insulation, it may take time
to activate the circuit breaker due to loads applied.