15
|
Piping installation
Installer and user reference guide
74
LREN8~12A7 + LRNUN5A7
CO₂ ZEAS outdoor unit and capacity up unit
4P704142-1 – 2022.08
Requirement
Limit
LREN*
LREN* + LRNUN5*
Piping length between
LREN*
and
LRNUN5*
Not specified, but piping must be
horizontal
Maximum branch piping length
▪
Example refrigeration side:
-
C+D+(E or F)
(a)
-
c+d+(e or f)
(a)
-
c+g
-
j
50 m
Maximum total piping length
180 m
Maximum height
difference
between outdoor
unit and indoor
unit
FN
Outdoor higher
than indoor
Example: H3≤Limit
35 m
(c)
Outdoor unit lower
than indoor unit
Example: H3≤Limit
10 m
Maximum height difference between
blower coil and showcase
▪
Example: H2≤Limit
5 m
(a)
Whichever is longer
(b)
For low load restrictions, see
"13.5.1 Constraints for refrigeration"
54].
(c)
You may have to install an oil trap. See
To install an oil trap
If the outdoor unit is installed higher than the refrigeration indoor unit, install an
oil trap in the gas piping every 5 meter. Oil traps will make the oil return more
easily.
a
c
b
c
a
Showcase
b
Height difference=5 m
c
Trap
The refrigerant suction piping must always run down: