16
|
Electrical installation
Installer and user reference guide
105
LREN8~12A7 + LRNUN5A7
CO₂ ZEAS outdoor unit and capacity up unit
4P704142-1 – 2022.08
16.2 Field wiring: Overview
g
F2
F1
F1
X1M (A1P)
F2 Q1 Q2
TO
MULTI UNIT
TO
OUT/D UNIT
TO
IN/D UNIT
L1 L2 L3 N
X1M
PE
X2M
C C1 W1 R P1 P2
2
1
3
X3M
F2
F1
F1
X1M (A1P)
F2 Q1 Q2
TO
MULTI UNIT
TO
OUT/D UNIT
TO
IN/D UNIT
L1 L2 L3 N
X1M
PE
X4M
C C1 W1 R P1 P2
2
1
3
X5M
220-240
V AC
220-240
V AC
220-240
V AC
12 V DC
12 V DC
12 V DC
12 V DC
220-240
V AC
220-240
V AC
220-240
V AC
220-240
V AC
DIII
DIII
f
g
f
d
e
d
e
a
b
d1 d2
h
h1
h2
d1 d2
X1M (A1P)
X5M
X4M
X1M
PE
X1M (A1P)
X2M
X1M
X3M
PE
3N~ 50 Hz
380-415 V AC
c1
c2
3N~ 50 Hz
380-415 V AC
c1
c2
k1
k
k2
k4
k3
k5
R1
R1
L N
X1M PE
X3M
A+ B- F1 F2
RS-485
DIII
X1M
X3M
PE
l
m
1N~ 50 Hz
220-240 V AC
c1
c2
a
Capacity up unit (LRNUN5A7Y1)
h2: Showcases (field supply)
b
Oudoor unit (LREN* )
k
Safety system (field supply).
Example:
c1
Overcurrent fuse (field supply)
k1: Control panel
c2
Earth leakage circuit breaker (field supply)
k2: CO
2
refrigerant leak detector
d
Alarm panel (field supply) for:
k3: Safety alarm (lamp)
d1: Caution output signal
k4: Ventilation (natural or mechanical)
d2: Warning output signal
k5: Shut off valve
e
Control panel (field supply) for operation output
signal
l
Communication box (BRR9B1V1)
f
Remote operation switch (field supply)
m
Monitoring system (field supply)
g
Remote low noise switch (field supply)
Wiring:
OFF: normal mode
ON: low noise mode
RS-485
RS-485 transmission wiring (mind polarity)
h
Operation output signal to expansion valves of all:
DIII
DIII transmission wiring (no polarity)
h1: Blower coils (field supply)
R1
Operation output