14
|
Unit installation
Installer and user reference guide
57
LREN8~12A7 + LRNUN5A7
CO₂ ZEAS outdoor unit and capacity up unit
4P704142-1 – 2022.08
14.1.1 Installation site requirements of the outdoor unit
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected
from easy access.
The equipment meets the requirements for commercial and light-industrial locations
when professionally installed and maintained.
CAUTION
This equipment is NOT intended for use in residential locations and will NOT
guarantee to provide adequate protection to radio reception in such locations.
NOTICE
If the equipment is installed closer than 30 m to a residential location, the
professional installer MUST evaluate the EMC situation before installation.
NOTICE
This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.
INFORMATION
The sound pressure level is less than 70 dBA.
INFORMATION
Also read the following requirements:
▪
General installation site requirements. See
"2 General safety precautions"
6].
▪
Service space requirements. See
145].
▪
Refrigerant
piping
requirements
(length,
height
difference).
See
"15.1.1 Refrigerant piping requirements"
72].
Choosing an appropriate site
▪
When installing, take strong winds, typhoons or earthquakes into account,
improper installation may result in the unit turning over.
▪
Make sure the installation site withstands the weight and vibration of the unit.
▪
Make sure the unit is level.
▪
Provide sufficient space around the unit for servicing and air circulation. See
"25.1 Service space: Outdoor unit"
▪
Heat exchanger fins are sharp and injury is possible. Choose an installation
location where there is no risk for injury (especially in areas where children play).
Refrigerant and ventilation
CAUTION
Excessive concentrations of refrigerant R744 (CO
2
) in a closed room can lead to
unconsciousness and oxygen deficiency. Take appropriate measures.
"To determine the minimum number of appropriate measures"
63].