16
|
Electrical installation
Installer and user reference guide
113
LREN8~12A7 + LRNUN5A7
CO₂ ZEAS outdoor unit and capacity up unit
4P704142-1 – 2022.08
Details – DIII transmission wiring
See
"16.4 Specifications of standard wiring components"
107].
Details – Remote operation switch
NOTICE
Remote operation switch
. The unit is factory-equipped with an operation switch
with which you can turn unit operation ON/OFF. If you want to remotely turn ON/
OFF operation of the capacity up unit, a remote operation switch is required. Use a
voltage-free contact for microcurrent (≤1 mA, 12 V DC). Connect to X3M/1+2 class II
construction, and set to "Remote".
REMOTE
OFF ON
S1S
S1S
Factory-equipped operation switch:
OFF: Unit operation turned OFF
ON: Unit operation turned ON
Remote: Unit controlled (ON/OFF) with remote operation switch
Wiring remote operation switch:
Wiring
Only use harmonised wire providing
double insulation and suitable for the
applicable voltage.
2-cord cable
0.75~1.25 mm²
Maximum wiring length
130 m
Details – Remote low noise switch:
NOTICE
Low noise switch
. If you want to remotely turn ON/OFF low noise operation, you
must install a low noise switch. Use a voltage-free contact for microcurrent (≤1 mA,
12 V DC).
Low noise switch
Mode
OFF
Normal mode
ON
Low noise mode
Wiring low noise switch:
Wiring
Only use harmonised wire providing
double insulation and suitable for the
applicable voltage.
2-cord cable
0.75~1.25 mm²