background image

7 Commissioning

Installation manual

26

LMSEY1A09/13 + LMSEY2A19/25

Daikin LMS

4P728170-1 – 2023.03

▪ 1: Only starting.

Only starting: secondary unit controllers will start to defrost at the
same  time  as  the  primary  unit  controller,  and  all  controllers  can
finish in different moments.

▪ 2: Start & Stop.

Start & Stop: secondary unit controllers will start to defrost at the
same  time  as  the  primary  unit  controller.  If  one  controller  ends
defrosting before the others, the corresponding defrost relay is de-
energised  and  the  dripping  phase  will  only  start  when  all  other
controllers have finished the defrosting phase.

C1
C2

C3

C4

CM

A

A1

B

B1

B1

min.

A

B

min.

A1

B

B1

C1
C2

C3

C4

CM

dS_1 = 0

dS_2 = 1

dS_3 = 2

dS_4 = 2

d2     = 0

dS_1 = 0

dS_2 = 1

dS_3 = 2

dS_4 = 2

d2     = 1

A

Start

A1

Start not synchronised

B

End synchronised

B1

End not synchronised

C1

Controller secondary unit 1

C2

Controller secondary unit 2

C3

Controller secondary unit 3

C4

Controller secondary unit 4

CM

Primary unit controller

dS1~4

Defrost synchronisation parameters

d2

Network end defrost synchronised for primary unit

Name

Description

Default

Min.

Max.

dS_1 Network defrost synchronised

for secondary unit controller 1.

▪ 0: 

No 

synchronisation

performed.

▪ 1: Only at start.

▪ 2: Start & stop.

0

0

2

dS_2 Network defrost synchronised

for secondary unit controller 2.

0

0

2

dS_3 Network defrost synchronised

for secondary unit controller 3.

0

0

2

dS_4 Network defrost synchronised

for secondary unit controller 4

0

0

2

d2

Network end defrost
synchronised for primary unit
controller.

0

0

1

Local defrosting on a LMSEY unit is still possible in two ways:

▪ Manually (from app, supervisory system or user interface).

▪ With  parameter  “dI”  (maximum  interval  between  consecutive

defrosts)  taking  control.  This  will  happen  when  a  network
connection  fault  occurs  that  lasts  longer  than  the  "dI"  parameter
setting. Therefore the "dI" parameter must always be set.

6.6

About the alarms

To check and reset alarms (error codes), see the operation manual.

7

Commissioning

CAUTION

Preliminary  electrical  system  checks  such  as  earth
continuity,  polarity,  resistance  to  earth  and  short  circuit
must  be  carried  out  by  using  a  suitable  test  meter  by  a
competent person.

WARNING

ONLY qualified persons should conduct commissioning.

Final checks for correct installation

Check that there is no air gap between unit and cold room
wall.

Check the labels of the wires connected to the door micro
switch and the door heater. The door heater wire is a live
wire,  while  the  micro  switch  wire  is  a  signal  wire.
Swapping the wires will cause serious damage to the unit.

Check that all covers are closed correctly.

Check  that  the  electrical  wiring  of  the  door  micro  switch,
door heater and cold room lamp are properly fixed to the
cold room panels.

Check  that  all  the  electrical  wiring  work  is  correctly
connected.

Check that all cable glands are properly tightened.

DANGER

   

Tripping  over  loose  wiring  can  tear  it  loose  and  cause
electrocution and fire.

Final checks for correct setup

Check that the programming logic is suitable to control the
unit and the system in question.

Check that the time has been set on the controller.

Check that the time bands have been set correctly.

Check  that  the  standard  display  (showing  the  setpoint)
has been set on the user terminal.

Check  that  the  appropriate  unit  of  measure  has  been  set
for the temperature probes (°C or °F).

Test run

Connect the unit's electrical plug to the mains outlet.

Turn on the unit.

Set the cold room temperature.

Check  that  the  setpoint  of  the  cold  room  temperature  is
reached.

Start defrost mode.

Check for water leaks.

Check  that  no  alarms  occur  on  the  user  interface  (see
user manual).

Switch off the unit.

Содержание LMSEY1A09AVM01

Страница 1: ...Installation manual Daikin LMS English Installation manual Daikin LMS LMSEY1A09AVM01 LMSEY1A13AVM01 LMSEY2A19AYE01 LMSEY2A25AYE01...

Страница 2: ...le units 25 6 6 About the alarms 26 7 Commissioning 26 8 Hand over to the user 27 9 Disposal 27 10 Technical data 27 10 1 Wiring diagram 27 10 2 Piping diagram 29 10 3 Weight 29 11 Glossary 29 1 About...

Страница 3: ...could result in electrical shock short circuit leaks fire or other damage to the equipment ONLY use accessories optional equipment and spare parts made or approved by Daikin CAUTION Wear adequate per...

Страница 4: ...bles and make sure they do NOT come in contact with the piping and sharp edges Make sure no external pressure is applied to the terminal connections Make sure to install earth wiring Do NOT earth the...

Страница 5: ...efrigerating appliances and ice makers with an incorporated or remote refrigerant unit or motor compressor EN 12100 Risk assessment Directive and regulations 2006 42 CE EN ISO 13857 2020 Safety Distan...

Страница 6: ...packaging bags so that nobody especially NOT children can play with them Possible consequence suffocation h i d b b Cardboard pillars d Pallet h Screws i Protection cover blue color 5 Remove the prote...

Страница 7: ...Insulation accessory e Cold room roof f Condenser fan g High pressure switch h Electronic expansion valve with firewall i Evaporator j Evaporator fan k Thermistor l Defrost coil for drain pan m Drain...

Страница 8: ...To install multiple units 415 4 5 Possible options for the unit INFORMATION Certain options may NOT be available in your country Three cable glands a b and c are provided to bring the option cables i...

Страница 9: ...ronment e g sea breeze atmosphere This to prevent corrosion caused by high levels of salt in the air which can shorten the life of the unit If outside air is sucked into the cold room the temperature...

Страница 10: ...e the blade is long enough to cut through the entire wall panel 5 3 Opening and closing the unit 5 3 1 To open the unit DANGER RISK OF ELECTROCUTION Do NOT leave the unit unattended when the service c...

Страница 11: ...st be removed See below for more information To prepare the cold room for wall mounting 1 Make a cutout in the front wall of the cold room The cutout x y will accommodate the unit evaporator protrusio...

Страница 12: ...old room 411 the optional insulation pad must be installed on the unit Refer to the installation instruction included in the insulation pad option 1 Install the insulation pad a at the back of the uni...

Страница 13: ...pad c Cutout 4 With the unit in place fix it with 4 screws through the fixing holes a b In case of saddle mounting method 1 If not already done position the unit on a lifting table and secure it with...

Страница 14: ...n the condenser part of the unit Most of the time this water evaporates in the overflow tank c that has hot refrigerant pipes d going through it This also works as a water cooling system for hot refri...

Страница 15: ...must be connected to their main PCB controllers 1 Open the unit condenser front plate and electrical box cover See 5 3 Opening and closing the unit 410 2 Connect the BMS connector J4 of the secondary...

Страница 16: ...suitable for 220 240 V and the total load of the control circuit must NOT exceed 4 A INFORMATION For the cold room lamp usually a LED bulb of 0 1 A is used with a maximum 0 3 A 4 Connect the wiring t...

Страница 17: ...X4M 32C X4M 33C X4M 34C X4M 35C X4M 36C X4M 37C X4M 38C X4M 39C X4M 40C X4M K3M 33 34 4 9 F3 6 3A F4 6 3A 5 2 5 2 5 6 5 7 5 7 5 7 5 6 5 6 5 4 5 4 5 9 5 9 5 9 5 9 5 10 5 9 5 8 5 8 5 3 HMI ACU Q1 d c a...

Страница 18: ...s 4 Select BLUETOOTH SCAN to view the controller devices available within a range of 10 m 5 Select the device to connect to Result BLE will blink on the user interface display to confirm that the conn...

Страница 19: ...n Max UoM Menu a App 5 b Unit of measure 0 C 1 F 0 0 1 Pro 6 Display decimal point 0 Yes 1 No 0 0 1 Pro t1 Display on user terminal 0 not configured 1 value of S1 2 value of S2 3 value of S3 4 value o...

Страница 20: ...m serial 0 no 1 yes 0 0 1 dFr b Defrost status 0 0 1 dFs b Defrost state idle dI b Maximum interval between consecutive defrosts 8 0 240 hours dP1 b Maximum defrost duration 45 1 240 min dP2 b Maximum...

Страница 21: ...0 1 FOE Logical status of the digital light output 0 0 1 FOG Logical status of the digital output 0 0 1 FOI Logical status of the digital output 0 0 1 FOI_1 Logical status of the digital output 0 0 1...

Страница 22: ...on for secondary unit 2 0 The controller regulates through the probe connected to itself 1 The controller regulates through the probe connected to the Primary unit 0 0 1 nrt_3 c Network temperature re...

Страница 23: ...ontrol setpoint 4 0 25 10 C F StH Setpoint for humidity 90 0 0 CtL Sv Virtual probe read only 20 2 0 0 Sv_1 Virtual probe secondary unit 1 read only 0 0 0 Sv_2 Virtual probe secondary unit 2 read only...

Страница 24: ...d Start timespan 5 day 0 00 00 0 00 00 23 59 59 tS5 time Start time datatype 5 0 00 00 0 00 00 23 59 59 tS6 d Start timespan 6 day 0 00 00 0 00 00 23 59 59 tS6 time Start time datatype 6 0 00 00 0 00...

Страница 25: ...tatus is open if the switch is open As for the lights also the door status is shared to all controllers Every controller knows if the door s is are open or not and each controller can perform the acti...

Страница 26: ...s will happen when a network connection fault occurs that lasts longer than the dI parameter setting Therefore the dI parameter must always be set 6 6 About the alarms To check and reset alarms error...

Страница 27: ...t must be done by an authorised area technical assistance service that has proper training equipment and instructions for the dismantling They are also responsible for reuse recycling and recovery CAU...

Страница 28: ...F3 Line aux fuse HMI User interface HMI cable User interface cable connection HPS1 High pressure switch 1 HPS2 High pressure switch 1 Symbol Meaning INV1 Inverter compressor 1 INV2 Inverter compresso...

Страница 29: ...Thermistor evaporator inlet Th6 B Thermistor evaporator outlet Th7 B Thermistor condenser 10 3 Weight Model Type Weight LMSEY1A09AVM01 A 52 kg LMSEY1A13AVM01 LMSEY2A19AYE01 B 83 5 kg LMSEY2A25AYE01 WA...

Страница 30: ...nal equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation Field supply Equipment NOT made by Daikin that...

Страница 31: ......

Страница 32: ...4P728170 1 2023 03 Copyright 2023 Daikin 4P728170 1 0000000N Verantwortung f r Energie und Umwelt...

Отзывы: