background image

6 Configuration

Installation manual

25

LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728170-1 – 2023.03

6.5.2

To activate the shared parameters for
multiple units

It  is  possible  to  share  some  parameters  between  the  primary  unit
controller and its secondary unit controllers. This way these settings
only have to be done on the primary unit.

The list of the shared parameters is:

▪ Setpoint,

▪ Differential,

▪ PID for compressor control (cdt, cPr, cti),

▪ PID for valve control (P4, P5,P6),

▪ Defrost parameters (dt1, dP1, dd, Fd),

▪ High and low alarms (AL, AH, ALA, AHA, A1),

▪ Date & time,

▪ Eco timebands (tS1-tS8, tE1-tE8).

INFORMATION

ONLY  the  primary  unit  controller  can  change  these
parameters when the sharing procedure is enabled. These
parameters  can’t  be  changed  on  secondary  unit
controllers.

It  is  possible  to  enable/disable  the  sharing  procedure  for  each
controller. To do this:

1

On the primary unit controller, set the parameter ESP_n of the
secondary unit controller to "1" to enable, "0" to disable.

▪ E.g. with ESP_1 = 0 and ESP_2 = 1, the sharing procedure is

only  enabled  with  secondary  unit  controller  2  and  not  with
secondary unit controller 1.

Name

Description

Default

Min.

Max.

ESP_1 Enable shared parameters for

secondary unit controller 1

0

0

1

ESP_2 Enable shared parameters for

secondary unit controller 2

0

0

1

ESP_3 Enable shared parameters for

secondary unit controller 3

0

0

1

ESP_4 Enable shared parameters for

secondary unit controller 4

0

0

1

6.5.3

To set the shared functions for multiple
units

Lights

Lights can be connected to all controllers in the network and the light
status is always synchronised. Each controller will turn the lights on
and off simultaneously.

The  time  during  which  the  light  stays  on  after  opening  and  closing
the  door  is  set  by  parameter  H14,  and  can  be  set  from  0  to
240 minutes. See 

"6.3 To change the parameters"

 [

4

 18].

Door open

The  door  microswitch  must  be  connected  to  the  primary  unit
controller in the network. Door status is "open" if the switch is open.

As  for  the  lights,  also  the  door  status  is  shared  to  all  controllers.
Every  controller  knows  if  the  door(s)  is/are  open  or  not,  and  each
controller  can  perform  the  actions  that  are  set  in  parameters  "DIE",
"DIP", "rIE" and "rIP".

Network temperature regulation

The  temperature  regulation  can  be  performed  in  two  ways
depending on the parameter "nrt" with the following values:

▪ 0: The relative controller regulates through the probe connected to

itself.

▪ 1: The relative controller regulates through the probe connected to

the primary unit controller.

The  network  logic  allows  avoiding  simultaneous  starts  of
compressors. Using the "SSd" parameter it is possible to set a delay
between starts of different LMSEY units.

If it is necessary to start several units at the same time, the first unit
to signal to start will be the first one to start. After "SSd" the next unit
will also start and so on (See the example below).

1

0

C1

C2

C3

C4

CM

sec.

A
B

SSd SSd SSd SSd

SSd

1

0

1

0

1

0

1

0

1

On

0

Off

A

Compressor status

B

Request status

C1

Compressor secondary unit 1

C2

Compressor secondary unit 2

C3

Compressor secondary unit 3

C4

Compressor secondary unit 4

CM

Compressor primary unit

SSd

Delay between start up [s]

Note: 

LM25AYE01 units have two compressors, but work

in a similar way.

Name

Description

Default

Min.

Max.

nrt_1

Network temperature regulation
for secondary unit 1.

▪ 0:  The  relative  controller

regulates  through  the  probe
connected to itself.

▪ 1:  The  relative  controller

regulates  through  the  probe
connected  to  the  primary  unit
controller.

0

0

1

nrt_2

Enable shared parameters for
secondary unit 2

0

0

1

nrt_3

Enable shared parameters for
secondary unit 3

0

0

1

nrt_4

Enable shared parameters for
secondary unit 4

0

0

1

SSd

Delay between the start up of
different compressors (in
seconds).

20

0

300

Network defrost

It  is  possible  to  enable/disable  this  functionality  for  each  controller
separately.

Defrost can be synchronised between the primary unit controller and
secondary unit controllers using parameters dS_1, dS_2, dS_3, and
dS_4 with the following values:

▪ 0: No synchronisation performed.

Содержание LMSEY1A09AVM01

Страница 1: ...Installation manual Daikin LMS English Installation manual Daikin LMS LMSEY1A09AVM01 LMSEY1A13AVM01 LMSEY2A19AYE01 LMSEY2A25AYE01...

Страница 2: ...le units 25 6 6 About the alarms 26 7 Commissioning 26 8 Hand over to the user 27 9 Disposal 27 10 Technical data 27 10 1 Wiring diagram 27 10 2 Piping diagram 29 10 3 Weight 29 11 Glossary 29 1 About...

Страница 3: ...could result in electrical shock short circuit leaks fire or other damage to the equipment ONLY use accessories optional equipment and spare parts made or approved by Daikin CAUTION Wear adequate per...

Страница 4: ...bles and make sure they do NOT come in contact with the piping and sharp edges Make sure no external pressure is applied to the terminal connections Make sure to install earth wiring Do NOT earth the...

Страница 5: ...efrigerating appliances and ice makers with an incorporated or remote refrigerant unit or motor compressor EN 12100 Risk assessment Directive and regulations 2006 42 CE EN ISO 13857 2020 Safety Distan...

Страница 6: ...packaging bags so that nobody especially NOT children can play with them Possible consequence suffocation h i d b b Cardboard pillars d Pallet h Screws i Protection cover blue color 5 Remove the prote...

Страница 7: ...Insulation accessory e Cold room roof f Condenser fan g High pressure switch h Electronic expansion valve with firewall i Evaporator j Evaporator fan k Thermistor l Defrost coil for drain pan m Drain...

Страница 8: ...To install multiple units 415 4 5 Possible options for the unit INFORMATION Certain options may NOT be available in your country Three cable glands a b and c are provided to bring the option cables i...

Страница 9: ...ronment e g sea breeze atmosphere This to prevent corrosion caused by high levels of salt in the air which can shorten the life of the unit If outside air is sucked into the cold room the temperature...

Страница 10: ...e the blade is long enough to cut through the entire wall panel 5 3 Opening and closing the unit 5 3 1 To open the unit DANGER RISK OF ELECTROCUTION Do NOT leave the unit unattended when the service c...

Страница 11: ...st be removed See below for more information To prepare the cold room for wall mounting 1 Make a cutout in the front wall of the cold room The cutout x y will accommodate the unit evaporator protrusio...

Страница 12: ...old room 411 the optional insulation pad must be installed on the unit Refer to the installation instruction included in the insulation pad option 1 Install the insulation pad a at the back of the uni...

Страница 13: ...pad c Cutout 4 With the unit in place fix it with 4 screws through the fixing holes a b In case of saddle mounting method 1 If not already done position the unit on a lifting table and secure it with...

Страница 14: ...n the condenser part of the unit Most of the time this water evaporates in the overflow tank c that has hot refrigerant pipes d going through it This also works as a water cooling system for hot refri...

Страница 15: ...must be connected to their main PCB controllers 1 Open the unit condenser front plate and electrical box cover See 5 3 Opening and closing the unit 410 2 Connect the BMS connector J4 of the secondary...

Страница 16: ...suitable for 220 240 V and the total load of the control circuit must NOT exceed 4 A INFORMATION For the cold room lamp usually a LED bulb of 0 1 A is used with a maximum 0 3 A 4 Connect the wiring t...

Страница 17: ...X4M 32C X4M 33C X4M 34C X4M 35C X4M 36C X4M 37C X4M 38C X4M 39C X4M 40C X4M K3M 33 34 4 9 F3 6 3A F4 6 3A 5 2 5 2 5 6 5 7 5 7 5 7 5 6 5 6 5 4 5 4 5 9 5 9 5 9 5 9 5 10 5 9 5 8 5 8 5 3 HMI ACU Q1 d c a...

Страница 18: ...s 4 Select BLUETOOTH SCAN to view the controller devices available within a range of 10 m 5 Select the device to connect to Result BLE will blink on the user interface display to confirm that the conn...

Страница 19: ...n Max UoM Menu a App 5 b Unit of measure 0 C 1 F 0 0 1 Pro 6 Display decimal point 0 Yes 1 No 0 0 1 Pro t1 Display on user terminal 0 not configured 1 value of S1 2 value of S2 3 value of S3 4 value o...

Страница 20: ...m serial 0 no 1 yes 0 0 1 dFr b Defrost status 0 0 1 dFs b Defrost state idle dI b Maximum interval between consecutive defrosts 8 0 240 hours dP1 b Maximum defrost duration 45 1 240 min dP2 b Maximum...

Страница 21: ...0 1 FOE Logical status of the digital light output 0 0 1 FOG Logical status of the digital output 0 0 1 FOI Logical status of the digital output 0 0 1 FOI_1 Logical status of the digital output 0 0 1...

Страница 22: ...on for secondary unit 2 0 The controller regulates through the probe connected to itself 1 The controller regulates through the probe connected to the Primary unit 0 0 1 nrt_3 c Network temperature re...

Страница 23: ...ontrol setpoint 4 0 25 10 C F StH Setpoint for humidity 90 0 0 CtL Sv Virtual probe read only 20 2 0 0 Sv_1 Virtual probe secondary unit 1 read only 0 0 0 Sv_2 Virtual probe secondary unit 2 read only...

Страница 24: ...d Start timespan 5 day 0 00 00 0 00 00 23 59 59 tS5 time Start time datatype 5 0 00 00 0 00 00 23 59 59 tS6 d Start timespan 6 day 0 00 00 0 00 00 23 59 59 tS6 time Start time datatype 6 0 00 00 0 00...

Страница 25: ...tatus is open if the switch is open As for the lights also the door status is shared to all controllers Every controller knows if the door s is are open or not and each controller can perform the acti...

Страница 26: ...s will happen when a network connection fault occurs that lasts longer than the dI parameter setting Therefore the dI parameter must always be set 6 6 About the alarms To check and reset alarms error...

Страница 27: ...t must be done by an authorised area technical assistance service that has proper training equipment and instructions for the dismantling They are also responsible for reuse recycling and recovery CAU...

Страница 28: ...F3 Line aux fuse HMI User interface HMI cable User interface cable connection HPS1 High pressure switch 1 HPS2 High pressure switch 1 Symbol Meaning INV1 Inverter compressor 1 INV2 Inverter compresso...

Страница 29: ...Thermistor evaporator inlet Th6 B Thermistor evaporator outlet Th7 B Thermistor condenser 10 3 Weight Model Type Weight LMSEY1A09AVM01 A 52 kg LMSEY1A13AVM01 LMSEY2A19AYE01 B 83 5 kg LMSEY2A25AYE01 WA...

Страница 30: ...nal equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation Field supply Equipment NOT made by Daikin that...

Страница 31: ......

Страница 32: ...4P728170 1 2023 03 Copyright 2023 Daikin 4P728170 1 0000000N Verantwortung f r Energie und Umwelt...

Отзывы: