Part
3. Commissioning Procedure
112
Design Guide
DCM014A51
Instance
#
Object Name (Sub_1)
Type
Instance
#
Object Name (Sub_2)
Type
200
S1_Condensing Pressure
AI
300
S2_Condensing Pressure
AI
201
S1_Evaporating Pressure
AI
301
S2_Evaporating Pressure
AI
202
S1_Condensing Temperature
AI
302
S2_Condensing Temperature
AI
203
S1_Evaporating Temperature
AI
303
S2_Evaporating Temperature
AI
204
S1_Inverter Compressor 1 Speed
AI
304
S2_Inverter Compressor 1 Speed
AI
205
S1_Inverter Compressor 2 Speed
AI
305
S2_Inverter Compressor 2 Speed
AI
206
S1_Fan Step
AI
306
S2_Fan Step
AI
207
S1_EV Position 1
AI
307
S2_EV Position 1
AI
208
S1_EV Position 2
AI
308
S2_EV Position 2
AI
209
S1_Hot Gas Temperature
(Compressor 1)
AI
309
S2_Hot Gas Temperature
(Compressor 1)
AI
210
S1_Hot Gas Temperature
(Compressor 2)
AI
310
S2_Hot Gas Temperature
(Compressor 2)
AI
211
S1_Liquid Pipe Temperature
AI
311
S2_Liquid Pipe Temperature
AI
212
S1_Liquid Pipe Temperature
(HX Upper)
AI
312
S2_Liquid Pipe Temperature
(HX Upper)
AI
213
S1_Liquid Pipe Temperature
(HX Lower)
AI
313
S2_Liquid Pipe Temperature
(HX Lower)
AI
214
S1_Liquid Pipe Temperature (Deicer)
AI
314
S2_Liquid Pipe Temperature
(Deicer)
AI
215
S1_Gas Pipe Temperature
(HX Upper)
AI
315
S2_Gas Pipe Temperature
(HX Upper)
AI
216
S1_Gas Pipe Temperature
(HX Lower)
AI
316
S2_Gas Pipe Temperature
(HX Lower)
AI
217
S1_Suction Temperature
AI
317
S2_Suction Temperature
AI
218
S1_Compressor Suction Temperature
AI
318
S2_Compressor Suction
Temperature
AI
219
S1_Subcool Inlet Temperature
AI
319
S2_Subcool Inlet Temperature
AI
220
S1_Subcool Outlet Temperature
AI
320
S2_Subcool Outlet Temperature
AI
221
S1_Subcool EV Position
AI
321
S2_Subcool EV Position
AI
Note: Shaded points are not available by default and will need to be enabled during the
iTM
BACnet®
Server Gateway commissioning.