Part
2. Functional Specifications
80
Design Guide
DCM014A51
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (-50 to 120[
℃
] / -58 to 248[
゚
F]).
24. M_Liquid Pipe Temperature (Deicer)
S1_Liquid Pipe Temperature (Deicer)
S2_Liquid Pipe Temperature (Deicer)
Member number: 114
(
M_Liquid Pipe Temperature (Deicer)
214
(
S1_Liquid Pipe Temperature (Deicer))
314
(
S2_Liquid Pipe Temperature (Deicer)
Object name:
M_Liquid Pipe Temperature (Deicer)
S1_Liquid Pipe Temperature (Deicer)
S2_Liquid Pipe Temperature (Deicer)
Object type:
Analog Input
Description:
Monitors the temperature of the outdoor unit liquid pipe heat
exchanger (for de-icing).
Present_Value property:
Temperature of the outdoor unit liquid pipe heat exchanger (for de-
icing)
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (-50 to 120[
℃
] / -58 to 248[
゚
F]).
25. M_Gas Pipe Temperature (HX Upper)
S1_Gas Pipe Temperature (HX Upper)
S2_Gas Pipe Temperature (HX Upper)
Member number: 115
(
M_Gas Pipe Temperature (HX Upper)
215
(
S1_Gas Pipe Temperature (HX Upper))
315
(
S2_Gas Pipe Temperature (HX Upper)
Object name:
M_Gas Pipe Temperature (HX Upper)
S1_Gas Pipe Temperature (HX Upper)
S2_Gas Pipe Temperature (HX Upper)
Object type:
Analog Input
Description:
Monitors the temperature of the outdoor unit gas pipe heat exchanger
(upper side).
Present_Value property:
Temperature of the outdoor unit gas pipe heat exchanger (upper side)
Remarks:
(1) Units are set to
℃
/
゚
F depending on the system settings.
(2) The number of valid digits is an integer for both Celsius and Fahrenheit.
(3) The value range is (-50 to 120[
℃
] / -58 to 248[
゚
F]).