5
c. Points for explanation about operations
2-4
NOTE TO THE INSTALLER
Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating differ-
ent functions, and adjusting the temperature) by having them carry out operations themselves while look-
ing at the manual.
3. SELECTING INSTALLATION SITE
〈
Hold the unit by the 4 lifting lugs when opening the box and moving it, and do not exert pressure on to any
other part piping (refrigerant, drain, etc.) or plastic parts.
If the temperature or humidity inside the ceiling might rise above 30°C or RH 80%, respectively, use the high-
humidity kit (sold separately) or add extra insulation to the main unit body.
Use glass wool or polyethylene foam as insulation and make sure it is at least 10mm thick and fits inside the
ceiling opening.
〉
The direction this product blows can be selected. However, a separately sold shut-off material kit is
needed in order to make the unit blow in two, three, or four (corner shut-off) directions.
(1) Select an installation location with the customer’s approval which matches the following condi-
tions.
• A location from which cool (warm) air will reach the whole room.
• A location with no objects blocking the air passage.
• A location where drainage can be done with no problem.
• A location strong enough to support the weight of the indoor unit.
• Locations where the wall is not significantly tilted.
• A location which leaves enough room for installation and service work.
• A location where there is no risk of flammable gas leaking.
• A location where the length of the indoor-outdoor piping is no longer than the tolerated length (see the
installation manual that came with the outdoor unit for details).
NOTE
• Leave 200 mm or more space where marked with the *, on sides where the air outlet is closed.
Model
H
FXZQ20·25·32·40·50
285 (Confirm the space of 295 or more)
The items with WARNING and CAUTION marks in the instruction manual are the items pertaining
to possibilities for bodily injury and material damage in addition to the general usage of the product.
Accordingly, it is necessary that you make a full explanation about the described contents and also ask
your customers to read the instruction manual.
H
1500
>
2500
>
1500
>
*
1500
>
*
1500
>
*
1500
>
*
1500
>
*
1500
>
*
Air
outlet
F
or installation
in high places
Air
inlet
Air
outlet
Fig. 1
Fig. 2
[Space required for installation] (mm)
01_EN_3P184443-5S.fm Page 5 Friday, October 16, 2015 6:44 PM