English
15
CAUTION
• Arrange the wires and fix a lid firmly so that the lid does not float during wiring work.
• Do not clamp remote controller wiring and transmission wiring together with power supply wiring. Doing so
may cause malfunction.
• Remote controller wiring and transmission wiring should be located at least 50 mm from power supply wir-
ing. Not following this guideline may result in malfunction due to electrical noise.
9. WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER
9-1
HOW TO CONNECT WIRINGS
Methods of wiring power supply, connecting transmission and remote controller wiring
• Power supply wiring and ground wire
Remove the control box lid and connect wires to the power supply terminal block (3P) inside. And connect
the ground wire to the terminal block. In doing this, pull the wires inside through the hole and fix the wires
securely with the included clamp (4).
Give enough slack to the wires between the clamp (4) and power supply terminal block. (Use Fig. 27 as a
guide and allow at least 80 mm for removing the sheath.)
• Transmission wiring and remote controller wiring
Remove the control box lid and pull the wires inside through the hole and connect to the terminal block for
remote controller (6P). (no polarity) Securely fix the remote controller wiring and the transmission wiring
with the included clamp (4).
Give enough slack to the wires between the clamp (4) and the terminal block for the remote controller.
• After connection, attach sealing material (12).
• Be sure to attach it to prevent the infiltration of water as well as any insects and other small creatures from
the outside. Otherwise a short-circuit may occur inside the control box.
CAUTION FOR WIRING
• For connection to the terminal block, use ring type crimp style terminals with insulation sleeve or insulate
the wirings properly.
• Connect the terminal as shown in Fig. 26.
• Do not carry out soldering finish when stranded wires are used. (Otherwise, the loosening of wires may
result in abnormal heat radiation.)
Insulation sleeve
Ring type crimp
style terminal
Wiring
Fig. 25
Fig. 26
Use wires the same in size
(if the air conditioner is in
simultaneous multi operation)