COMPUTERISED CONTROL (FORCED OFF AND ON/OFF OPERATION)
(1)
Wire specifications and how to perform wiring
• Connect the input from outside to terminals T1 and T2 of the terminal board for remote controller.
(2)
Actuation
• The following table explains FORCED OFF and ON/OFF OPERATIONS in response to input A.
(3)
How to select FORCED OFF and ON/OFF OPERATION
• Turn the power on and then use the remote controller to select operation.
9-5
CENTRALIZED CONTROL
• For centralized control, it is necessary to designate the group No. For details, refer to the manual of each
optional controllers for centralized control.
10. INSTALLATION OF THE DECORATION PANEL
Caution:
With a wireless remote controller, field setting and test operation cannot be performed without
attaching the decoration panel.
<Read “12. TEST OPERATION” before making a test run without attaching the decorated panels.>
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space between the unit body and decoration
panel.
11. FIELD SETTINGS
CAUTION
When performing field setting or test operation without attaching the decoration panel, do not
touch the drain pump. This may cause electric shock.
• Check that the outdoor unit has been wired properly.
(1) Make sure the control box lids are closed on the indoor and outdoor units.
(2) Field settings must be made from the remote controller and in accordance with installation con-
ditions.
• Settings can be made by changing the “Mode No.”, “FIRST CODE NO.” and “SECOND CODE NO.”.
• The “Field Settings” included with the remote control lists the order of the settings and method of oper-
ation.
Setting is made in all units in a group. To set for individual indoor units or to check the setting, use the
mode No. (with “2” in upper digit) in parentheses ( ).
11-1 SETTING AIR OUTLET DIRECTION
• See the installation manual included with the sealing material of air discharge outlet kit, sold separately
and technical guide, for ceiling height settings for two and three-direction air discharge.
(The SECOND CODE NO. is factory set to “01” (all round outlet) before shipping.)
Wire specification
Sheathed vinyl cord or cable (2 wire)
Gauge
0.75 - 1.25 mm
2
Length
Max. 100 m
External terminal
Contact that can ensure the minimum applicable
load of 15V DC, 1 mA.
FORCED OFF
ON/OFF OPERATION
Input “ON” stops operation (impossible by remote controllers).
Input OFF
→
ON turns ON unit.
Input OFF enables control by remote controller
Input ON
→
OFF turns OFF unit.
FORCED
OFF
T2
T1
F2
Input A