WIRING EXAMPLE AND HOW TO SET 
THE REMOTE CONTROLLER

9-1

HOW TO CONNECT WIRINGS 

(Remove the electrical components box lid and wire as shown in 
the figure below.)

Routing power supply wiring and transmission wiring

Let the power supply wiring with a conduit pass through one of 
the holes on the side cover, and let the transmission wiring with 
a conduit pass through another hole.

• For protection from uninsulated live parts, thread the power 

supply wiring or the transmission wiring through the included 
insulation tube and secure it with the included clamp.

CAUTION

• Be sure to attach the sealing material or putty (field supplied) 

to hole of wiring to prevent the infiltration of water as well as 
any insects and other small creatures from outside. Other-
wise a short-circuit may occur inside the electrical compo-
nents box.

• When clamping the wires, be sure no pressure is applied to 

the wire connections by using the included clamping material 
to make appropriate clamps. Also, when wiring, make sure 
the lid on the electrical components box fits snugly by arrang-
ing the wires neatly and attaching the electrical components 
box lid firmly. When attaching the electrical components box 
lid, make sure no wires get caught in the edges. Pass wiring 
through the wiring through holes to prevent damage to them.

• Make sure the remote controller wiring, the wiring between 

the units, and other electrical wiring do not pass through the 
same locations outside of the unit, separating them by at 
least 2in., otherwise electrical noise (external static) could 
cause mistaken operation or breakage. 

[ PRECAUTIONS ] 

1.

Use round crimp-style terminals for connecting wires to the 
power supply terminal block. 

If unavailable, observe the following points when wiring.
• Do not connect wires of different gauge to the same 

power supply terminal.
(Looseness in the connection may cause overheating.)

• Use the specified electric wire. Connect the wire securely to 

the terminal. Lock the wire down without applying excessive 
force to the terminal. (Tightening torque: 0.97ft·lbf ±10 %)

2. Tightening torque for the terminal screws.

• Use the correct screwdriver for tightening the terminal 

screws. If the blade of screwdriver is too small, the head 
of the screw might be damaged, and the screw will not be 
properly tightened.

• If the terminal screws are tightened too hard, screws 

might be damaged.

• Refer to the table below for the tightening torque of the 

terminal screws.

3. Do not connect wires of different gauge to the same ground-

ing terminal. Looseness in the connection may deteriorate 
protection.

4. Outside of the unit, keep transmission wiring at least 2in. 

away from power supply wiring. The equipment may mal-
function if subjected to electrical (external) noise. 

5. For remote controller wiring, refer to the “INSTALLATION 

MANUAL OF REMOTE CONTROLLER” attached to the 
remote controller. 

6.

Never connect power supply wiring to the terminal 
block for remote controller wiring. A mistake of the sort 
could damage the entire system.

7. Use only specified wire and tightly connect wires to terminals. 

Be careful wires do not place external stress on terminals. 
Keep wiring in neat order and so as not to obstruct other equip-
ment such as popping open the electrical components box lid. 
Make sure the lid closes tight. Incomplete connections could 
result in overheating, and in worse case, electric shock or fire.

Electrical 
components 
box lid

Transmission 
wiring (*)

Ground wiring

Power supply 
wiring (*)

(Field wiring)

Remote controller 
wiring (*)

(Field wiring)

(Field wiring)

Wiring (*)

(Remote controller 
 and transmission)

Wire locking 
bracket

Clamp
(accessory(8))

Conduit
(Field supply) 

Lock nut
(Field supply)

Insulation tube
(accessory (2))

Clamp
(accessory (8))

Power supply wiring 

or

Transmission wiring

(3in.)

Clamp (accessory (8))

Power supply 
terminal block

Terminal block for 
remote controller

Remote
controller wiring

X2M

X1M

Transmission wiring

Power supply wiring 
and ground wiring

Insulation tube
(accessory (2))

Insulation 
tube 
(accessory (2))

Ground 
terminal

Electric wire

Round crimp-style terminal

Attach insulation sleeve

Terminal

Size

Tightening torque (ft·lbf)

Terminal block for remote controller (6P)

M3.5

0.58 - 0.72

Power supply terminal block

Ground terminal

M5

M5

1.76 - 2.15

2.23 - 3.01

01_EN_3P086156-13Y.fm  Page 8  Wednesday, September 16, 2009  2:22 PM

Содержание FXMQ72MVJU

Страница 1: ...LATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE...

Страница 2: ...installation work check that the re frigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause se r...

Страница 3: ...R 410A is a blend the required additional refriger ant must be charged in its liquid state If the refrigerant is charged in a state of gas its composition can change and the system will not work prope...

Страница 4: ...ling the indoor unit Entrust installation to the place of purchase or a qualified ser viceman Improper installation could lead to leaks and in worse cases electric shock of fire Use only parts provide...

Страница 5: ...rference or noise Depending on the radio waves a distance of 3 3ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether the ceiling is strong enoug...

Страница 6: ...not possible if the types of refrigerant are not the same CAUTION Use a pipe cutter and flare suitable for the type of refrig erant Apply ester oil or ether oil inside the flare portions before conne...

Страница 7: ...zing is done without nitrogen gas blowing a large amount of oxide film develops inside the piping and could cause system malfunction When brazing the refrigerant piping only begin brazing after having...

Страница 8: ...tiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping between the outdoor unit and a...

Страница 9: ...97ft lbf 10 2 Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged...

Страница 10: ...F2 Control box L1L2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 L1L2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 L1 Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor u...

Страница 11: ...Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp o...

Страница 12: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0909 HT 3P086156 13Y EM09A017 00_CV_3P086156 13Y fm Page 2 Wednesday September 9 2009 2 52 PM...

Отзывы: