9-2 WIRING EXAMPLE 

• Fit the power supply wiring of each unit with a switch and fuse 

as shown in the drawing.

 

COMPLETE SYSTEM EXAMPLE (3 SYSTEMS) 

1. When using 1 remote controller for 1 indoor unit. (Nor-

mal operation)

2. For group control or use with 2 remote controllers

3. When including BS unit

[ PRECAUTIONS ] 

1. A single switch can be used to supply power to units on the 

same system. However, branch switches and branch 
ground fault circuit interrupters must be selected carefully. 

2. Do not ground the equipment on gas pipes, water pipes or 

lightning rods, or crossground with telephones. Improper 
grounding could result in electric shock.

9-3

CONTROL BY 2 REMOTE CONTROLLERS (Con-
trolling 1 indoor unit by 2 remote controllers)

• When using 2 remote controllers, one must be set to “MAIN” 

and the other to “SUB”.

MAIN/SUB CHANGEOVER

(1) Insert a 

screw driver into the recess between the upper 

and lower part of remote controller and, working from the 2 
positions, pry off the upper part. 
The remote controller PC board is attached to the upper 
part of remote controller. 

(2) Turn the MAIN/SUB changeover switch on one of the two 

remote controller PC boards to “S”. 
(Leave the switch of the other remote controller set to “M”.)

Power supply wiring

Transmission wiring

Switch

Fuse

Power supply

Main
switch

Remote controller

Indoor unit

BS unit
(Only for
Heat
recovery system)

L1 L2

L1

IN/D OUT/D

F1 F2 F1 F2

Control box

L1 L2

L1L2

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

L1L2

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

L1L2

L1L2

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

L1

Outdoor unit

No. 1
System

Indoor 
unit A

Indoor 
unit B

Indoor 
unit C

Most
downstream
Indoor unit 

Power supply

208-230V

60Hz

Power supply

208-230V

60Hz

Power supply

208-230V

60Hz

Power supply

208-230V

60Hz

L2

L2

L1 L2

L1 L2

L1 L2

Indoor unit A

IN/D OUT/D

F

1

F

2

F

1

F

2

Control box

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

P

1

P

2

F

1

F

2

T

1

T

2

P

1

P

2

F

1

F

2

T

1

T

2

P

1

P

2

F

1

F

2

T

1

T

2

P

1

P

2

P

1

P

2

L1 L2

Outdoor 

unit

No. 2
System

Indoor unit B

Indoor unit C

Most 
downstream
indoor unit

For use with 2
remote controllers

Power supply

208-230V

60Hz

Power supply

208-230V

60Hz

Power supply

208-230V

60Hz

Power supply

208-230V

60Hz

Note: It is not necessary to designate indoor unit address 

when using group control. 
The address is automatically set when power is 
activated.

Fig. 3

L1 L2

L1 L2

L1 L2

L1 L2

IN/D OUT/D

F

1

F

2

F

1

F

2

IN/D

OUT/D

F

1

F

2

F

1

F

2

L1 L2

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

BS unit

No. 3
System

Outdoor unit

Power supply

208-230V

60Hz

Indoor unit A

Most 
downstream
indoor unit

Power supply

208-230V

60Hz

Control box

Control box

IN/D

OUT/D

F

1

F

2

F

1

F

2

BS unit

Control box

L1

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

L2

L1 L2

L1 L2

Upper part of 
remote controller

Lower part of 
remote controller

Insert the screwdriver here and gently work 
off the upper part of remote controller.

Only one remote 
controller needs to be 
changed if factory 
settings have 
remained untouched.

(Factory setting)

S

M

S

S

M

Remote controller 
PC board

01_EN_3P086156-13Y.fm  Page 9  Wednesday, September 16, 2009  2:22 PM

Содержание FXMQ72MVJU

Страница 1: ...LATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE...

Страница 2: ...installation work check that the re frigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause se r...

Страница 3: ...R 410A is a blend the required additional refriger ant must be charged in its liquid state If the refrigerant is charged in a state of gas its composition can change and the system will not work prope...

Страница 4: ...ling the indoor unit Entrust installation to the place of purchase or a qualified ser viceman Improper installation could lead to leaks and in worse cases electric shock of fire Use only parts provide...

Страница 5: ...rference or noise Depending on the radio waves a distance of 3 3ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether the ceiling is strong enoug...

Страница 6: ...not possible if the types of refrigerant are not the same CAUTION Use a pipe cutter and flare suitable for the type of refrig erant Apply ester oil or ether oil inside the flare portions before conne...

Страница 7: ...zing is done without nitrogen gas blowing a large amount of oxide film develops inside the piping and could cause system malfunction When brazing the refrigerant piping only begin brazing after having...

Страница 8: ...tiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping between the outdoor unit and a...

Страница 9: ...97ft lbf 10 2 Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged...

Страница 10: ...F2 Control box L1L2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 L1L2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 L1 Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor u...

Страница 11: ...Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp o...

Страница 12: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0909 HT 3P086156 13Y EM09A017 00_CV_3P086156 13Y fm Page 2 Wednesday September 9 2009 2 52 PM...

Отзывы: