background image

English

6

CAUTION

Over-tightening may damage the flare and cause a refriger-
ant leakage.

Use “ Table 2 ” as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque will sud-
denly increase. From that position, tighten the nut to the angle 
shown on “ Table 2 ”.

• After checking the pipe-connection for gas leakage, be sure 

to insulate the liquid and gas piping, referring to the figure 
below.

• Wrap the sealing pad (field supply) only around the insulation 

for the joints on the gas piping side. 

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

NOTE

• Attached piping is needed for connecting gas piping. Use 

attached piping according to the size of the piping to be con-
nected.
When connecting the included piping, use the included pip-
ing flange hex bolts accessory (9) and spring washers acces-
sory (10).

• Connect refrigerant piping and branching according to the 

attached installation manuals that come with the outdoor 
unit.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-
ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filler metal (BCuP-2/
B-Cu93P-710/795) which does not require flux.
(Flux has extremely harmful infulence on refrigerant piping 
sysems. For instance, if the chlorine based flux is used, it 
will cause pipe corrosion or, in particular, if the flux contains 
fluorine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 2.90PSI with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping.

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to 
install the unit without a torque wrench, you may follow the 
installation method mentioned below.

After the work is finished, make sure to check that 
there is no gas leak.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque suddenly 
increases. From that position, further tighten the flare nut 
the angle shown below:

Table 2

7.

DRAIN PIPING WORK

〈〈

Rig the drain pipe as shown below and take measures 

against condensation. Improperly rigged piping could lead 
to leaks and eventually wet furniture and belongings.

〉〉

〈〈

Insulate the drain hose inside the building.

〉〉

(1) Carry out the drain piping.

Indoor units to be 

connected

Gas piping diameter

Liquid piping 

diameter

FXMQ72MVJU

φ

3/4

Use attached piping.

φ

3/8

FXMQ96MVJU

φ

7/8

Use attached piping.

Sealing pad

(Field supply)

Insulation for fitting 
(Field supply)

Gas pipe

Liquid pipe

(for gas line)

Clamp

(accessory (8))

Pipe size

Further tightening 

angle

Recommended arm length of 

tool

φ 

1/4”

60 to 90 degrees

Approx. 5-7/8in.

φ 

3/8”

60 to 90 degrees

Approx. 7-7/8in.

φ 

1/2”

30 to 60 degrees

Approx. 9-13/16in.

φ 

5/8”

30 to 60 degrees

Approx. 11-3/16in.

Nitrogen

Refrigerant 
piping

Part to be 
brazed 

Taping

Pressurereducing valve

hands 
valve

Nitrogen

Bottom of unit

Attached drain hose

01_EN_3P086156-13Y.fm  Page 6  Wednesday, September 16, 2009  2:22 PM

Содержание FXMQ72MVJU

Страница 1: ...LATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE...

Страница 2: ...installation work check that the re frigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause se r...

Страница 3: ...R 410A is a blend the required additional refriger ant must be charged in its liquid state If the refrigerant is charged in a state of gas its composition can change and the system will not work prope...

Страница 4: ...ling the indoor unit Entrust installation to the place of purchase or a qualified ser viceman Improper installation could lead to leaks and in worse cases electric shock of fire Use only parts provide...

Страница 5: ...rference or noise Depending on the radio waves a distance of 3 3ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether the ceiling is strong enoug...

Страница 6: ...not possible if the types of refrigerant are not the same CAUTION Use a pipe cutter and flare suitable for the type of refrig erant Apply ester oil or ether oil inside the flare portions before conne...

Страница 7: ...zing is done without nitrogen gas blowing a large amount of oxide film develops inside the piping and could cause system malfunction When brazing the refrigerant piping only begin brazing after having...

Страница 8: ...tiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping between the outdoor unit and a...

Страница 9: ...97ft lbf 10 2 Tightening torque for the terminal screws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged...

Страница 10: ...F2 Control box L1L2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 L1L2 L1L2 P1 P2 P1 P2 F1 F2 T1 T2 L1 Outdoor unit No 1 System Indoor unit A Indoor unit B Indoor u...

Страница 11: ...Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp o...

Страница 12: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0909 HT 3P086156 13Y EM09A017 00_CV_3P086156 13Y fm Page 2 Wednesday September 9 2009 2 52 PM...

Отзывы: