12
(2) The fan speed for this indoor unit is preset to provide
standard external static pressure.
• If higher or lower external static pressure is required,
reposition the adapter for the PC board. Refer to “9. WIR-
ING EXAMPLE AND HOW TO SET THE REMOTE CON-
TROLLER”.
(3) Install the suspension bolts. (Use bolts of 3/8”
diameter.)
Use a hole-in-anchor, sunken insert, sunken anchor for
existing ceilings, and a sunken insert, sunken anchor or
other part to be procured in the field to reinforce the ceiling
to bearing the weight of the unit.
5. INDOOR UNIT INSTALLATION
〈〈
Installing optional accessories (except for the decoration
panel) before installing the indoor unit is easier.
As for the parts to be used for installation work, be sure to use
the provided accessories and specified parts designated by our
company.
〉〉
(1) Install the indoor unit temporarily.
• Attach the hanger bracket
to the suspension bolt. Be
sure to fix it securely by
using a nut and washer
from the upper and lower
sides of the hanger
bracket.
FXSQ30 · 36 · 48MVJU
57 7/16
For mounting air inlet panel directly
Model
A (in.)
FXSQ12MVJU
24
FXSQ18MVJU
29 7/8
FXSQ24MVJU
41 11/16
FXSQ30 · 36 · 48MVJU
57 7/16