7. DRAIN PIPING WORK

(1) Carry out drain piping.

Carry out drain piping so that drainage can ensured.

Drain piping can be connected from the following directions: For right rear/right side, refer to 

Fig. 18

 of 

“6. REFRIGERANT PIPING WORK”

, and for left rear/left side, refer to 

Fig. 21

.

When conducting left rear/left side drain piping, remove the protection net. Then, remove the drain socket 
cap and insulation material applied to left side drain socket and apply them to the right side drain socket. 
When doing this, insert the drain socket cap all the way in to prevent a water leakage.
After the drain hose (1) (accessory) installing, attach the protection net by reversing the steps taken to 
remove it. 

(Refer to Fig. 22)

Select the piping diameter equal to or larger than that of the drain hose (1) (accessory) (polyvinyl chloride 
piping, nominal diameter 20mm, outside diameter 26mm). 

Install the drain piping as short as possible with downward inclination of 1/100 or more and without where 
air may stagnate. 

(Refer to Fig. 23 and 24)

(It may cause abnormal sound such as bubbling noise)

CAUTION

If drain stagnates in the drain piping, the piping may be clogged.

Back side (sheet metal)
Detach parts

Putty or insulation
(field supply)

Left side
Drain piping

Left side
Detach parts

Left rear side
Drain piping

Fig. 21

Good

Wrong

Supports

1-1.5m

Downward inclination 
of 1/100 or more

Do not lift

Make sure there 
is no slack

Make sure it is 
not in the water

Fig. 23

Fig. 24

Protection net

Fixing 
screw for
protection net

Fig. 22

01_EN_3P249378-8N.fm  Page 14  Saturday, September 29, 2012  3:02 PM

Содержание FXHQ32AVEB

Страница 1: ...S CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERI MENTO FUTURO LEES DEZE INSTRUCTIES...

Страница 2: ...ich if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert...

Страница 3: ...ontrol box lid is not in place overheat of the terminals electric shocks or a fire may be caused If refrigerant gas leaks during installation work ventilate the area immediately Toxic gas may be produ...

Страница 4: ...itioner while looking at the operation manual Instruct the customer how to operate the air conditioner particularly cleaning of the air filters operation pro cedures and temperature adjustment For sel...

Страница 5: ...at stated in the manufacturer s label on the air conditioner Does not operate burnout Are you sure that there is no wrong wiring or piping or no loose wiring Does not operate burnout Is earthing compl...

Страница 6: ...east 1 meter away from televisions or radios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor u...

Страница 7: ...378 324 270 375 398 377 260 Type 63 1270 1230 533 479 425 530 553 532 415 Type 100 1590 1550 693 639 585 690 713 692 575 Fig 3 F 690 Unit dimension 210 D C A Unit dimension B Hanging bolt pitch View f...

Страница 8: ...rface and install the attached resin bushing 10 3 Remove the hanger Loosen 2 bolts for installing the hanger at both sides M8 4 places at left and right within 10mm Refer to Fig 7 and 8 Remove the fix...

Страница 9: ...d installation parts and specified parts 1 Fix the hanger to the hanging bolt Refer to Fig 10 CAUTION For safety make sure to use a washer for hanger 3 accessory and fix by double nuts firmly 2 Lift u...

Страница 10: ...ecurely If not insulated it may cause water leakage For gas piping use insulation material of which heat resistant temperature is not less than 120 C For use under high humidity strengthen the insulat...

Страница 11: ...the angle shown in Table 2 After the work is finished check securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in mal function...

Страница 12: ...ndoor unit side Do not leave clearance Wrap from the root of the indoor unit Sealing material Small 9 accessory Bring the seam to the top Flare nut connection Piping insulating material field supply F...

Страница 13: ...panel penetration cover as it was before removed put the horizontal blade motor and ther mistor lead through the clamp of the top panel penetration cover and fix Refer to Fig 16 and 19 When doing thi...

Страница 14: ...it will be affected badly 3 When carrying out leakage test of refrigerant piping and the indoor unit after the installation of indoor unit is finished confirm the connecting outdoor unit installation...

Страница 15: ...en to remove it Refer to Fig 22 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl chloride piping nominal diameter 20mm outside diameter 26mm Install the...

Страница 16: ...ause abnormal noise such as bubbling noise If the drain hose 1 is deflected it may damage the suction grille Install supports at a distance of 1 to 1 5m so that the piping may not deflect Refer to Fig...

Страница 17: ...in pump kit 2 After piping is finished check if the drain flows smoothly Gradually put about 0 6 liter of water for drain confirmation into the drain pan from the air outlet Refer to Fig 29 After the...

Страница 18: ...r piping Hard vinyl tubes are not effective earths Lightning conductor or telephone earth wiring Electric potential may rise abnormally if struck by a lightning bolt Do not turn on the power supply br...

Страница 19: ...ning the terminal screws If an improper screw driver is used it may damage the screw head and a proper tightening cannot be carried out If a terminal is over tightened it may be damaged Refer to the t...

Страница 20: ...xture 11 and clamp 4 so that no tension will be given to the wiring transmission part Refer to Fig 32 WARNING When wiring form the wirings orderly so that the control box lid can be securely fastened...

Страница 21: ...Keep the distance of 50mm or more between the low voltage wiring remote controller wiring and the high voltage wiring power supply wiring earth wiring at anywhere outside the indoor unit If both the w...

Страница 22: ...ote controller Remote controller Remote controller L N L N L N option option option P1P2 P1P2 Outdoor unit Note It is not needed to set the indoor unit address when using group control It is automatic...

Страница 23: ...he wiring connection method 2 Carry out additional wiring from the remote controller 2 Sub to the terminals P1 P2 for remote controller wiring on the terminal block X1M in the control box CAUTION When...

Страница 24: ...ill be as the table shown below 3 How to choose FORCED OFF or ON OFF OPERATION For choosing FORCED OFF or ON OFF OPERATION setting by remote controller is required Refer to 10 FIELD SETTING AND TEST O...

Страница 25: ...ation state Carry out setting at 3 places Mode No FIRST CODE No and SECOND CODE No The settings shown by in the table indicate those when shipped from the factory The method of setting procedure and o...

Страница 26: ...CODE No to the number shown in the Table 5 according to the amount of dust or pollution in the room Though the indoor unit is equipped with the long life filter it is necessary to periodically clean t...

Страница 27: ...carrying out test operation After test operation is completed before delivering the air conditioner to the customer confirm that the control box lid the air filter and suction panel are attached In ad...

Страница 28: ...OR SWITCH WIRELESS ADDRESS SET A2P A3P BS1 H1P H2P H3P H4P SS1 SS2 WIRING DIAGRAM CONNECTOR FOR OPTIONAL PARTS INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANC...

Страница 29: ...1209 HT 3P249378 8N EM12A009 00_CV_3P249378 8N fm Page 2 Sunday September 30 2012 4 47 PM...

Отзывы: