FXFSQ-AVM EDFMT391769A
50
3P468397-1D
17
<<If test operation is required before mounting the
decoration panel, “10. FIELD SETTING AND TEST
OPERATION” can be carried out before “9. MOUNTING
DECORATION PANEL”.>>
CAUTION
In case of a wireless remote controller, unless the decoration
panel is mounted,
field
setting and test opera tion cannot be
carried out.
Refer to the installation manual attached to the decoration
panel.
•
After the decoration panel is mounted, check if no clearance
exists between the panel and the unit.
•
If test operation is carried out before mounting the decoration
panel, check the swing blade action after the panel is
mounted.
<<Refer to also the installation manual attached to the
outdoor unit.>>
CAUTION
Before carrying out
field
setting, check the items mentioned in
the clause 2 “
1. Items to be checked after the installation
work is completed” on page 3.
•
Check if all the installation and piping works for the air
conditioner are completed.
•
Check if the control box lids of the air conditioner are closed.
< FIELD SETTING >
<<After turn on the power supply, carry out
field
setting
from the remote controller according to the installation
state.>>
•
Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.”
and “SECOND CODE No.”.
The settings shown by “
” in the table indicate those
when shipped from the factory.
•
The method of setting procedure and operation is shown in
the installation manual attached to the remote controller.
(Note) Though setting of “Mode No.” is carried out as a group,
if you intend to carry out individual setting by each
indoor unit or
confi
rmation after setting, carry out
setting with the Mode No. shown in the parenthesis ( ).
•
In case of remote control, for changeover of input to
FORCED OFF or to ON/OFF OPERATION.
[1]
Enter into the
field
setting mode with the remote controller.
[2] Select Mode No. “12”.
[3] Set the FIRST CODE No. to “1”.
[4-1] For FORCE OFF, set the SECOND CODE No. to “01”.
[4-2] For ON/OFF OPERATION, set the SECOND CODE
No. to “02”.
(It is set to FORCE OFF when shipped from the factory.)
•
Ask your customer to keep the manual attached to the remote
controller together with the operation manual.
•
Do not carry out settings other than those shown in the table.
Terminal for remote
controller wiring (P1, P2)
No polarity
Remote
controller 2
(Sub)
Remote
controller 1
(Main)
Terminal block
(X1M)
< Caution >
•
When using the group control and the 2 remote control-
lers control at the same time, connect the remote control-
ler 2 (Sub) to the indoor unit at the end of the crossover
wiring (the largest No.).
(Refer to Fig. 25)
Indoor unit 1
Indoor unit 2
Indoor unit
largest No.
Remote
controller 2
(Sub)
Crossover
wiring (Remote
controller)
Remote
controller 1
(Main)
Fig. 25
8-7 FOR CENTRALIZED CONTROL
•
When centralized equipment (such as centralized controller)
is used for control, it is required to set the group No. on the
remote controller.
For details, refer to the manuals attached to the centralized
equipment.
•
Connect the centralized equipment to the indoor unit
connected to the remote controller.
8-8 FOR REMOTE CONTROL (FORCE OFF OR ON /
OFF OPERATION)
(1) Wiring method and
specification
•
Remote control is available by connecting the external
input to the terminal T1 and T2 on the terminal block for
remote controller and transmission wiring (X1M).
F2 T1 T2
FORCED
OFF
Input A
Wiring
Sheathed vinyl
cord or 2 core
cable
Wiring size
0.75-1.25 mm
2
Wiring length
Max. 100 m
External
contact spec
Contact that can
make and break
the min. load of
DC 15 V · 1 mA
(2) Actuation
•
Input A of FORCED OFF and ON/OFF OPERATION will
be as the table shown below.
Input A = ON
Input A = OFF
In case of FORCED
OFF
Remote controller
prohibited
Remote controller
permitted
In case of ON/OFF
OPERATION
Operation
Stop
(3) How to choose FORCED OFF or ON/OFF OPERATION
•
For choosing FORCED OFF or ON/OFF OPERATION,
setting by remote controller is required.
(Refer to “
10. FIELD SETTING AND TEST OPERATION”)
9. MOUNTING DECORATION PANEL
10. FIELD SETTING AND TEST OPERATION
Содержание FXFSQ-AVM
Страница 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...
Страница 2: ......
Страница 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...
Страница 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...
Страница 13: ...FXFSQ AVM EDFMT391769A 11 3 2 Standard Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112987A Unit mm...
Страница 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...
Страница 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...
Страница 16: ...FXFSQ AVM EDFMT391769A 14 3 3 Designer Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112988A Unit mm...
Страница 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...
Страница 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...
Страница 19: ...FXFSQ AVM EDFMT391769A 17 3 4 Auto Grille Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112991A Unit mm...
Страница 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...
Страница 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...
Страница 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...
Страница 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...
Страница 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...
Страница 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...
Страница 55: ......