FXFSQ-AVM EDFMT391769A

50

3P468397-1D

17

<<If test operation is required before mounting the 

decoration panel, “10. FIELD SETTING AND TEST 

OPERATION” can be carried out before “9. MOUNTING 

DECORATION PANEL”.>>

 CAUTION

In case of a wireless remote controller, unless the decoration 
panel is mounted, 

field

 setting and test opera tion cannot be 

carried out.

Refer to the installation manual attached to the decoration 
panel.

After the decoration panel is mounted, check if no clearance
exists between the panel and the unit.

If test operation is carried out before mounting the decoration
panel, check the swing blade action after the panel is
mounted.

<<Refer to also the installation manual attached to the 

outdoor unit.>>

 CAUTION

Before carrying out 

field

 setting, check the items mentioned in 

the clause 2 “

1. Items to be checked after the installation 

work is completed” on page 3.

Check if all the installation and piping works for the air
conditioner are completed.

Check if the control box lids of the air conditioner are closed.

< FIELD SETTING >

<<After turn on the power supply, carry out 

field

 setting 

from the remote controller according to the installation 

state.>>

Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.”
and “SECOND CODE No.”. 
The settings shown by “ 

 ” in the table indicate those 

when shipped from the factory.

The method of setting procedure and operation is shown in
the installation manual attached to the remote controller.
(Note)  Though setting of “Mode No.” is carried out as a group,

if you intend to carry out individual setting by each 
indoor unit or 

confi

rmation after setting, carry out 

setting with the Mode No. shown in the parenthesis ( ). 

In case of remote control, for changeover of input to
FORCED OFF or to ON/OFF OPERATION. 
[1]

Enter into the 

field

 setting mode with the remote controller.

[2] Select Mode No. “12”.
[3] Set the FIRST CODE No. to “1”.
[4-1] For FORCE OFF, set the SECOND CODE No. to “01”.
[4-2] For ON/OFF OPERATION, set the SECOND CODE
        No. to “02”. 
(It is set to FORCE OFF when shipped from the factory.)

Ask your customer to keep the manual attached to the remote
controller together with the operation manual.

Do not carry out settings other than those shown in the table.

Terminal for remote 

controller wiring (P1, P2)

No polarity

Remote 

controller 2

(Sub)

Remote 

controller 1

(Main)

Terminal block 

(X1M)

< Caution >

When using the group control and the 2 remote control-
lers control at the same time, connect the remote control-
ler 2 (Sub) to the indoor unit at the end of the crossover
wiring (the largest No.). 

(Refer to Fig. 25)

Indoor unit 1

Indoor unit 2

Indoor unit 

largest No.

Remote 

controller 2 

(Sub)

Crossover 

wiring (Remote 

controller)

Remote 

controller 1 

(Main)

Fig. 25

8-7  FOR CENTRALIZED CONTROL

When centralized equipment (such as centralized controller)
is used for control, it is required to set the group No. on the
remote controller. 
For details, refer to the manuals attached to the centralized
equipment.

Connect the centralized equipment to the indoor unit
connected to the remote controller.

8-8  FOR REMOTE CONTROL (FORCE OFF OR ON /

OFF OPERATION) 

(1) Wiring method and 

specification

Remote control is available by connecting the external
input to the terminal T1 and T2 on the terminal block for
remote controller and transmission wiring (X1M).

F2 T1 T2

FORCED

OFF

Input A

Wiring  

Sheathed vinyl 
cord or 2 core 
cable

Wiring size

0.75-1.25 mm

2

Wiring length

Max. 100 m

External  
contact spec

Contact that can 
make and break 
the min. load of 
DC 15 V · 1 mA

(2) Actuation

Input A of FORCED OFF and ON/OFF OPERATION will
be as the table shown below.

Input A = ON

Input A = OFF

In case of FORCED 
OFF

Remote controller 

prohibited

Remote controller 

permitted

In case of ON/OFF 
OPERATION

Operation

Stop

(3) How to choose FORCED OFF or ON/OFF OPERATION

For choosing FORCED OFF or ON/OFF OPERATION,
setting by remote controller is required.
(Refer to “

10. FIELD SETTING AND TEST OPERATION”)

9. MOUNTING DECORATION PANEL

10. FIELD SETTING AND TEST OPERATION

Содержание FXFSQ-AVM

Страница 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...

Страница 2: ......

Страница 3: ...s 21 6 Electric Characteristics 22 7 Safety Devices Setting 23 8 Capacity Tables 24 8 1 Cooling Capacity for Te Auto 24 8 2 Cooling Capacity for Te 6 C 24 8 3 Cooling Capacity for Te 9 C 25 8 4 Heatin...

Страница 4: ...ty index 25 31 25 40 50 62 5 80 100 125 140 FXFSQ 25AVM 32AVM 40AVM 50AVM 63AVM 80AVM 100AVM 125AVM 140AVM FXFSQ for Thailand 25AVS 32AVS 40AVS 50AVS 63AVS 80AVS 100AVS 125AVS 140AVS FXFSQ for Indones...

Страница 5: ...es Fuse Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950...

Страница 6: ...use Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950 50 950 9...

Страница 7: ...Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 950 950 50 950...

Страница 8: ...devices Fuse Fuse Refrigerant control Electronic expansion valve Electronic expansion valve Decoration panel option Model BYCQ125EAF BYCQ125EAF Colour Fresh white Fresh white Dimensions H W D mm 50 95...

Страница 9: ...rigerant control Electronic expansion valve Decoration panel option Model BYCQ125EAF Colour Fresh white Dimensions H W D mm 50 950 950 Air filter Resin net with mould resistance Mass kg 5 5 Standard a...

Страница 10: ...FXFSQ AVM EDFMT391769A 8 3 Dimensions 3 1 Standard Panel with Sensing Sensor FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112984A Unit mm...

Страница 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...

Страница 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...

Страница 13: ...FXFSQ AVM EDFMT391769A 11 3 2 Standard Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112987A Unit mm...

Страница 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...

Страница 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...

Страница 16: ...FXFSQ AVM EDFMT391769A 14 3 3 Designer Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112988A Unit mm...

Страница 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...

Страница 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...

Страница 19: ...FXFSQ AVM EDFMT391769A 17 3 4 Auto Grille Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112991A Unit mm...

Страница 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...

Страница 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...

Страница 22: ...0AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 12 7 6 4 FXFSQ...

Страница 23: ...FXFSQ AVM EDFMT391769A 21 5 Wiring Diagrams FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112965A...

Страница 24: ...FXFSQ AVM EDFMT391769A 22 6 Electric Characteristics FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM C 3D112911...

Страница 25: ...ector Drain pump thermal protector C Model FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM Printed circuit board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Fan motor thermal protector Drain pump thermal protector C...

Страница 26: ...length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 1...

Страница 27: ...city kW SHC Sensible heat capacity kW Notes 1 These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of...

Страница 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...

Страница 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...

Страница 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...

Страница 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...

Страница 32: ...FXFSQ AVM EDFMT391769A 30 10 Centre of Gravity FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 4D052237S Unit mm...

Страница 33: ...long life filter Note 9 10 KAFP55H160H Branch duct chamber Note 4 KDJP55C80 Insulation kit for high humidity Note 9 11 KDTP55K80 C 3D112950A Notes 1 When installing designer panel body height ceiling...

Страница 34: ...Branch duct chamber Note 4 KDJP55C160 Insulation kit for high humidity Note 9 11 KDTP55K160 C 3D112950A Notes 1 When installing designer panel body height ceiling required dimension is 42 mm higher th...

Страница 35: ...tor for electrical appendices Note 1 KRP4AA53 Installation box for adaptor printed circuit board KRP1H98A Note 2 3 Remote sensor for indoor temperature KRCS01 5B External control adaptor for outdoor u...

Страница 36: ...cident due to oxygen de ciency Be sure to use only the speci ed parts and accessories for installation work Failure to use the speci ed parts may result in the air conditioner falling down water leaka...

Страница 37: ...angers 4 places and do not apply force to other parts particularly refrigerant piping drain piping and resin parts Make sure to check in advance that the refrigerant to be used for installation work i...

Страница 38: ...If you wish to use a remote controller that is not listed in Table 2 on page 3 select a suitable remote controller after consulting catalogs and technical materials CARRY OUT THE WORK GIVING CAUTION T...

Страница 39: ...e ensured Where the ceiling lower surface is not remarkably inclined Where there is strength to withstand the mass of the indoor unit If the strength is the indoor unit may vibrate and get in contact...

Страница 40: ...controller on site Refer to the section 10 FIELD SETTING AND TEST OPERATION 3 Direction of the air discharge Select the number of directions of the optimum air discharge for the shape or the position...

Страница 41: ...olt Ceiling slab Long nut or turn buckle Ceiling surface Note The above shown parts are all eld supply It is easy to attach the optional parts except for decoration panel before installing the indoor...

Страница 42: ...Check the level of the unit Refer to Fig 9 5 Remove the washer clamp 7 used for preventing the washer for hanger 3 from dropping and tighten the upper side nut Level Vinyl tube Maintaining horizontal...

Страница 43: ...Fig 11 Then turn the nut 3 to 4 times with your hand and screw in the nut Torque wrench Spanner Flare nut Union joint Fig 10 Coat the ared inner surface only with ether oil or ester oil Fig 11 Table 3...

Страница 44: ...the outdoor unit installation manual or technical document for refrigerant piping 5 In case of refrigerant shortage due to forgetting additional refrigerant charge etc it will result in malfunction su...

Страница 45: ...Put the metal clamp 2 to the taped hose end and tighten the metal clamp 2 with torque 1 35 0 15 N m 135 15 N cm CAUTION Do not tighten the metal clamp 2 with the torque more than the value The drain h...

Страница 46: ...splashing water on the electric components such as drain pump and con rm drainage by operating the indoor unit under cooling mode according to 10 FIELD SETTING AND TEST OPERATION Refer to Fig 18 100 P...

Страница 47: ...dedicated circuit Insuf cient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a re Make sure to install an earth leakage breaker Failure to do s...

Страница 48: ...Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFQ25AVM FXFQ32AVM FXFQ40AVM FXFQ50AVM FXFQ63AVM FXF...

Страница 49: ...g transmission wiring connecting method Power supply wiring earth wiring Pull the wiring through the wiring penetrating hole high voltage After connecting the power supply wiring to L N on the power s...

Страница 50: ...led off After the wirings are clamped cut off the extra part Sheath peeling off allowance P1 P2 F1 F2 T1 T2 10 15 mm Remote controller wiring Transmission wiring Forced off R10 or more Clamp 4 Remote...

Страница 51: ...troller 2 Sub to the terminals P1 P2 for remote controller wiring on the terminal block X1M in the control box Wiring penetrating hole Power supply wiring earth wiring or remote controller wiring tran...

Страница 52: ...he SECOND CODE No to 01 4 2 For ON OFF OPERATION set the SECOND CODE No to 02 It is set to FORCE OFF when shipped from the factory Ask your customer to keep the manual attached to the remote controlle...

Страница 53: ...ng blade 10 1 SETTING CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 5 Table 5 Setting Ceiling height m Mode No FIRST CODE No SECOND CODE No 25 80 type 100...

Страница 54: ...ner until the interior work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives used for the interior...

Страница 55: ......

Страница 56: ...parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation...

Отзывы: