FXFSQ-AVM EDFMT391769A
41
3P468397-1D
8
6. REFRIGERANT PIPING WORK
•
For the outdoor unit refrigerant piping, refer to the installation
manual attached to the outdoor unit.
•
Carry out insulation of both gas and liquid refrigerant piping
securely. If not insulated, it may cause water leakage. For
gas piping, use insulation material of which heat resistant
temperature is not less than 120°C.
For use under high humidity, strengthen the insulation
material for refrigerant piping. If not strengthened, the
surface of insulation material may sweat.
•
Before installation work, make sure that the refrigerant
is R410A. (Unless the refrigerant is R410A, the nor mal
operation cannot be expected.)
CAUTION
This
air
conditioner
is
a
dedicated
model
for
new
refrigerant
R410A.
Make
sure
to
meet
the
requirement
s
shown
below
and
carry
out
installation
work.
•
Use
dedicated
piping
cutters
and
tools for
R410A.
•
When
making
a
connection,
coat
the
inner
surface
only
with
ether
oil
or
ester
oil.
•
Use
only
the
nuts
attached
to
the
air
conditioner.
If
other
nuts
are
used,
it
may
cause
refrigerant
leakage.
•
To
prevent
contamination
or
moisture
from
gettin
g
into
the
piping,
take
measures
such
as
pinch
ing
o
r
taping
the
pipings.
D
o
no
t
mi
x
substanc
e
othe
r
tha
n
th
e specified
refrigerant
such
as
air
into
the
refrigeration
circuit
.
If
the
refrigerant
leaks
during
the
work,
ventilate
th
e
room.
•
The refrigerant is pre-charged in the outdoor unit.
•
When connecting the pipings to the air conditioner, make
sure to use a spanner and a torque wrench as shown in
Fig.
10.
•
•
For the dimension of
part and the tightening torque,
refer to the Table 3.
For flare nut, use the mounting one to the body.
•
When making a
connection, coat the
inner
surface only with ether oil or ester oil.
(Refer
to
Fig.
11)
Then, turn the
nut 3 to 4 times with your hand and
screw in the nut.
Torque wrench
Spanner
Flare nut
Union joint
Fig.
10
Coat the flared inner surf
ace
only with ether oil or ester oil
Fig.
11
Table 3
Piping
size
(mm)
Tightening
torque
(N·m)
Dimension for
processing
flare
A (mm)
Flare shape
φ
6.4
15.7 ± 1.5
8.9 ± 0.2
R0.6
±
0.2
90°±2°
A
45°±2°
φ
9.5
36.3 ± 3.6
13.0 ± 0.2
φ
12.7
54.9 ± 5.4
16.4 ± 0.2
φ
15.9
68.6 ± 6.8
19.5 ± 0.2
CAUTION
Do
not
have
oil
adhere
to
the
screw
part
of resin
parts.
If oil adheres, it may weaken the strength of screwed part.
Do
not
tighten
nuts
too
tight.
If a
flare
nut cracks, the refrigerant may leak.
•
If there is no torque wrench, use Table 4 as a rule of
thumb.
When tightening a
nut with a spanner harder and
harder, there is a point where the tightening torque
suddenly increases.
From that position, tighten the nut additionally the angle
shown in Table 4.
After the work is
check securely that there is no
gas leak.
If the nut is not tightened as instructed, it may cause slow
refrigerant leak and result in malfunction (such as does
not cool or heat).
Table 4
Piping size
(mm)
Tightening
angle
Recommended arm length of
tool used
φ
6.4
60° - 90°
approx. 150 mm
φ
9.5
60° - 90°
approx. 200 mm
φ
12.7
30° - 60°
approx. 250 mm
φ
15.9
30° - 60°
approx. 300 mm
CAUTION
Insulation
of
piping
must
be
carried
out
up
to
the
connection
inside
the
casing.
If the piping is exposed to the atmosphere, it may cause
sweating, burn due to touching the piping, electric shocks or
a
fire
due to the wiring touching the piping.
•
After leak test, referring to
Fig.
12, insulate both the gas
and liquid piping connection with the attached joint
insulating material (8) and (9) to prevent the pipings from
getting exposed.
Then, tighten the both ends of insulating material with the
clamp (4).
•
Wrap the sealing material (Medium-1, 2) (11) (12) around
the joint insulating material (8) and (9)
nut section),
both the gas and liquid piping.
•
Make sure to bring the seam of joint insulating material (8)
and (9) to the top.
Содержание FXFSQ-AVM
Страница 1: ...FXFSQ AVM EDFMT391769A 201802 Engineering Data 50 60 Hz...
Страница 2: ......
Страница 11: ...FXFSQ AVM EDFMT391769A 9 FXFSQ63AVM FXFSQ80AVM 3D112982A Unit mm...
Страница 12: ...FXFSQ AVM EDFMT391769A 10 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112977A Unit mm...
Страница 13: ...FXFSQ AVM EDFMT391769A 11 3 2 Standard Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112987A Unit mm...
Страница 14: ...FXFSQ AVM EDFMT391769A 12 FXFSQ63AVM FXFSQ80AVM 3D112983A Unit mm...
Страница 15: ...FXFSQ AVM EDFMT391769A 13 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112979A Unit mm...
Страница 16: ...FXFSQ AVM EDFMT391769A 14 3 3 Designer Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112988A Unit mm...
Страница 17: ...FXFSQ AVM EDFMT391769A 15 FXFSQ63AVM FXFSQ80AVM 3D112985A Unit mm...
Страница 18: ...FXFSQ AVM EDFMT391769A 16 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112980A Unit mm...
Страница 19: ...FXFSQ AVM EDFMT391769A 17 3 4 Auto Grille Panel FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM 3D112991A Unit mm...
Страница 20: ...FXFSQ AVM EDFMT391769A 18 FXFSQ63AVM FXFSQ80AVM 3D112986A Unit mm...
Страница 21: ...FXFSQ AVM EDFMT391769A 19 FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM 3D112981A Unit mm...
Страница 28: ...FXFSQ AVM EDFMT391769A 26 9 Sound Levels FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM 4D112880A 4D112874A...
Страница 29: ...FXFSQ AVM EDFMT391769A 27 FXFSQ50AVM FXFSQ63AVM 4D112898A 4D112879B...
Страница 30: ...FXFSQ AVM EDFMT391769A 28 FXFSQ80AVM FXFSQ100AVM 4D112878B 4D509733A...
Страница 31: ...FXFSQ AVM EDFMT391769A 29 FXFSQ125AVM FXFSQ140AVM 4D509732A 4D509731A...
Страница 55: ......