background image

[Washer clamp (7) fixing method]

Washer clamp (7)
(accessory) 

Upper side nut

Insert

Fig. 8

(2)   

• 

The installation pattern paper (5) is matched to the ceil-
ing opening dimension. 

For the height of ceiling lower surface from the floor 
level, confirm with the builder of ceiling.

• 

The center of the ceiling opening is shown in the instal-
lation pattern paper (5).
The center of the indoor unit is indicated as triangle 
marks on the sides and bottom of the unit and those on 
the installation pattern paper (5).

• 

Put the installation pattern paper (5) to the indoor unit 
with four screws (6).
At this time, put the installation pattern paper (5) to the 
indoor unit with the triangle marks on the indoor unit and 
those on the installation pattern paper (5) aligned.

Installation 

pattern 

paper (5)

(accessory)

[Installation of the installation pattern paper]

Center of 

ceiling opening

Screw (6)
(accessory)

Screw (6)
(accessory)

Center of the 

indoor unit

Center mark 

of the unit

< Installation work after the ceiling work is finished >
(3)  
Adjust so that the unit will be properly positioned. 

( Refer to 

“4. PREPARATION BEFORE INSTALLATION 

– (1)” )

• 

Using the Installation guide (15) allows you to check the 
positions from the underside of the unit to the lower ceil-
ing surface.

Apply the short 
side of the 
cut-out section.

Lower ceiling 

surface

Installation guide (15)

Underside 

of the unit

(4)  Check the level of the unit. (Refer to Fig. 9)

(5)  Remove the washer clamp (7) used for preventing the 

washer for hanger (3) from dropping and tighten the upper 
side nut.

(6)  Remove the installation pattern paper (5).

Level

Vinyl tube

[Maintaining horizontality]

Fig. 9

 CAUTION

• 

Install the indoor unit leveled. 
If the indoor unit is inclined and the drain piping side gets 

high, it may cause malfunction of a float switch and results 

in water leakage.

• 

Attach nuts on the upper and lower side of hanger. 
If there is no upper nut and the lower nut is over-tightened, 
the hanger and the top plate will deform and cause abnormal 
sound.

•  Do not insert materials other than that specified into 

the clearance between the hanger and the washer for 

hanger (3). 
Unless the washers are properly attached, the hanging 
bolts may come off from the hanger.

 WARNING

The indoor unit must be securely installed on a place 

that can withstand the mass. 

If the strength is insufficient, the indoor unit may fall down 

and cause injuries.

6.  REFRIGERANT PIPING WORK

• 

For the outdoor unit refrigerant piping, refer to the installation 
manual attached to the outdoor unit.

• 

Carry out insulation of both gas and liquid refrigerant piping 
securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 120°C. 
For use under high humidity, strengthen the insulation 
material for refrigerant piping. If not strengthened, the 
surface of insulation material may sweat.

• 

Before installation work, make sure that the refrigerant 
is R410A. (Unless the refrigerant is R410A, the nor mal 
operation cannot be expected.)

 CAUTION

This air conditioner is a dedicated model for new re-

frigerant R410A. Make sure to meet the require ments 

shown below and carry out installation work.

•  Use dedicated piping cutters and flaring tools for 

R410A.

•  When making a flare connection, coat the flared inner 

surface only with ether oil or ester oil.

•  Use only the flare nuts attached to the air conditioner. 

If other flare nuts are used, it may cause refrigerant 

leakage.

• 

To prevent contamination or moisture from getting 

into the piping, take measures such as pinch ing or 

taping the pipings.

3P335596-2D        English 

6

Содержание FXFQ25SVM

Страница 1: ...ensing FXFQ25SVM FXFQ63SVM FXFQ32SVM FXFQ80SVM FXFQ40SVM FXFQ100SVM FXFQ50SVM FXFQ125SVM INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR...

Страница 2: ...h may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work...

Страница 3: ...ance that the refrigerant to be used for installation work is R410A The air conditioner will not properly operate if a wrong refrigerant is used For installation of the outdoor unit refer to the insta...

Страница 4: ...ing operation and the warm air discharge during the heating operation Does the indoor unit makes unpleasant sound of air discharge Have you explained how to operate the air conditioner showing the ope...

Страница 5: ...perature heat generating equipment is in stalled Each sensor has been set so that the center of the sensing area is located in the center of the product 800 mm above the floor in case of the infrared...

Страница 6: ...to reinforce the ceiling framework to keep the level of the ceiling and prevent vibration of the ceiling For details consult with the builder and interior designer 3 Install the hanging bolts Use M8...

Страница 7: ...n piping side gets high it may cause malfunction of a float switch and results in water leakage Attach nuts on the upper and lower side of hanger If there is no upper nut and the lower nut is over tig...

Страница 8: ...rench use Table 3 as a rule of thumb When tightening a flare nut with a spanner harder and harder there is a point where the tightening torque sud denly increases From that position tighten the nut ad...

Страница 9: ...nitrogen flow through the piping is approximately 0 02 MPa a pressure that makes one feel like breeze and can be obtained through a pres sure reducing valve 2 Do not use flux when brazing refrigerant...

Страница 10: ...the tip of the metal clamp 2 inward as shown Refer to Fig 16 In case of sticking vinyl tape Tightened part approx 90 Stick vinyl tape without tearing the sealing material Large 10 Vinyl tape In case...

Страница 11: ...ng the drainage of water refer to Fig 20 and attach the sealing material 14 to perform the thermal insulation of the drain socket Sealing material 14 accessory Fig 20 When the electric wiring work is...

Страница 12: ...nit always wiring the indoor unit to the terminal indicated with the same symbol on the terminal block If the wiring and the piping are connected to the different indoor units and operated it will res...

Страница 13: ...ning cannot be car ried out If a terminal is over tightened it may be damaged Refer to the table shown below for tightening torque of terminals Tightening torque N m Terminal block for remote controll...

Страница 14: ...supply wiring high voltage R10 or more R10 or more Strand the wirings after sheath is peeled off After the wirings are clamped cut off the extra part After the wirings are clamped cut off the extra pa...

Страница 15: ...L Remote controller option Remote controller option Remote controller option L N L N L N P1P2 F1 F2 T1 T2 P1P2 P1P2 F1 F2 T1 T2 P1P2 P1P2 F1 F2 T1 T2 P1P2 No 2 system When carrying out group control o...

Страница 16: ...ore 9 MOUNTING DECORATION PANEL CAUTION In case of a wireless remote controller unless the decoration panel is mounted field setting and test opera tion cannot be carried out Refer to the installation...

Страница 17: ...cleaning indication is not necessary such as the case of periodical clean ing being carried out TEST OPERATION After cleaning the indoor unit inside carry out test operation according to installation...

Страница 18: ......

Страница 19: ......

Страница 20: ...1310 FS 3P335596 2D EM13A007...

Отзывы: