• VRV Systems • Indoor Unit
5
• Indoor Unit • Wall mounted unit • FXAQ-P
2
Specifications
(6) The sound pressure level is measured via a microphone at 1m distance of the unit.
(7) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(8) Maximum allowable voltage range variation between phases is 2%.
(9) MCA/MFA: MCA = 1.25 x FLA
(10) MFA
≤
4 x FLA
(11) Next lower standard fuse rating minimum 16A
(12) Select wire size based on the value of MCA
(13) Instead of a fuse, use a circuit breaker
(14) Use a circuit breaker instead of a fuse.