• VRV
®
Systems • Indoor Units
3
• Indoor Units • Wall Mounted Unit • FXAQ-MAVE9
1
Specifications
3
1
1-2 ELECTRICAL SPECIFICATIONS (50HZ)
FXAQ20MAVE9
FXAQ25MAVE9
FXAQ32MAVE9
FXAQ40MAVE9
FXAQ50MAVE9
FXAQ63MAVE9
Power Supply
Name
VE
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps (MCA)
A
0.3
0.4
0.4
0.4
0.4
0.6
Maximum fuse amps (MFA)
A
15
Full load amps (FLA)
A
0.2
0.3
0.3
0.3
0.3
0.5
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ)
FXAQ20MAVE9
FXAQ25MAVE9
FXAQ32MAVE9
FXAQ40MAVE9
FXAQ50MAVE9
FXAQ63MAVE9
Power Supply
Name
VE
Phase
1~
Frequency
Hz
60
Voltage
V
220
Current
Minimum circuit amps (MCA)
A
0.3
0.3
0.4
0.4
0.4
0.6
Maximum fuse amps (MFA)
A
15
Full load amps (FLA)
A
0.2
0.2
0.3
0.3
0.3
0.5
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker