5 Commission the fan coil unit
Test operation before installing decoration panel
1
Open the water inlet valve(s).
2
Open the water outlet valve(s).
3
Set to cooling operation with the remote controller and start operation by pushing
ON/OFF
button.
4
Press
Inspection/Test Operation
button
4 times and operate at
Test Operation
mode for 3 minutes.
5
Press
Inspection/Test Operation
button
and operate normally.
6
Confirm function of unit according to the operation manual.
7
Turn off the main power supply after operation.
Test operation after installing decoration panel
1
Open the water inlet valve(s).
2
Open the water outlet valve(s).
3
Set to cooling operation with the remote controller and start operation by pushing
ON/OFF
button.
4
Press
Inspection/Test Operation
button
4 times (2 times for wireless remote
controller) and operate at
Test Operation
mode for 3 minutes.
5
Push
air flow direction adjust
button
to make sure the unit is in operation.
6
Press
Inspection/Test Operation
button
and operate normally.
7
Confirm function of unit according to the operation manual.
Handover to the user
5.4
Handover to the user
Once the test run is finished and the unit operates properly, fill in the sheet “Handover of the