Installation manual
12
FWF
Fan coil units
4PW64524-1 – 09.2010
4 Install the fan coil unit
1
Make the ceiling opening needed for installation where applicable. (For existing
ceilings.)
■
Refer to the paper pattern for installation (delivered with the unit) for the ceiling
opening dimensions.
■
Create the ceiling opening required for installation.
■
After making an opening in the ceiling, it may be necessary to reinforce the
suspended ceiling frame to keep the ceiling level and to prevent it from vibrating.
Consult the builder for details.
2
Install the suspension bolts. (Use either a M8~M10 size bolt.)
Use anchors for existing ceilings, and a sunken insert, sunken anchors or other field
supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the
unit. The distance between the suspension bolts is marked on the paper pattern for
installation (delivered with the unit). Refer to it to check for points requiring reinforcing.
Adjust clearance from the ceiling before proceeding further. See installation example in
figure below:
c
b
d
e
a
50 - 100
Fig. 4.4: Installing the suspension bolts
a
Ceiling slab
b
Anchor
c
Long nut or turn-buckle
d
Suspension bolt
e
Suspended ceiling
Information
■
All the above parts are field supplied.
■
For installation other than standard installation, contact your local DAIKIN
dealer for advice.
Fix the unit
4.4
Fix the unit
Caution
To avoid injury, do not touch the air inlet or aluminium fins of the unit.
When installing optional equipment, also read the installation manual of the optional
equipment. Depending on the field conditions, it may be easier to install optional equipment
before the unit is installed. However, for existing ceilings, always install fresh air intake kit
before installing the unit. For more information, refer to
“Install optional equipment” on
page 25
.