4 Install the fan coil unit
■
Use the specified electric wire (refer to
“Field wiring specifications” on page 8
). Connect
the wire securely to the terminal. Lock the wire down without applying excessive force
to the terminal. Use the appropriate tightening torque:
Tightening torque (N·m)
Terminal block for remote controller
0.79~0.97
Terminal block for power supply
1.18~1.44
Notice
Never connect the unit transmission wiring to the remote controller wiring. This
connection could cause irreparable damage to the entire system.
: Terminal
RED
: Red
YLW
: Yellow
: Connector
BLK
: Black
GRN
: Green
: Wire connector
WHT
: White
BLU
: Blue
: Field wiring
ORG
: Orange
A1P, A2P
Printed circuit board
C1
Capacitor (M1F)
F1U
Fuse (F5A, 250 V)
HAP
Light emitting diode (service monitor green)
KPR
Magnetic relay (M1P)
M1F
Motor (indoor fan)
M1P
Motor (drain pump)
M1S
Motor (swing flap)
Q1M
Thermo switch (M1F embedded)
Q1D1
Field earth leak detector (Max. 300 mA)
R1T
Thermistor (air)
R2T, R3T
Thermistor
S1L
Float switch
T1R
Transformer (220-240 V/22 V)
V1TR
Phase control circuit
X1M, X2M
Terminal strip
Table 4.1: Tightening torque
■
Remote controller wiring should be located at least 50 mm away from the unit
transmission wiring and other wiring. Failure to observe this guideline may result in
malfunction due to electrical noise.
■
For the remote controller wiring, refer to the installation manual of the remote controller
delivered with the remote controller.
■
Keep wiring in neat order so that wires do not obstruct other equipment or force the
control box cover to pop open. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worst case, electric shock or fire.
Wiring diagram
Refer to the wiring diagram sticker on the unit (on the inside of the control box cover).