5 Installation
Installation manual
22
FWE03~11D
Fan coil units
3P443944-5P – 2021.12
4
Fix the cables to the partition plate. Make sure that long
reminder cables are fixed tightly with a cable clamp in the new
position.
5
Fix the removed parts to the unit.
WIRING DIAGRAM
4D121422-1
AC SYSTEM SUPPL
Y
NEUTRAL CAP
ACIT
OR
PROTECT
OR EARTH
EARTH SELF-OPERA
TING
THERMAL
PROTECT
OR
FIELD WIRING FAN MOT
OR
GREEN
/ YELLOW
FUSE TERMINAL
STRIP
LOWEST SPEED HIGHEST SPEED
* For the power requirements, refer to the name plate.
L N
C1
Q1M
M GRN/YL
W
F1U X1M
1 5
GRN RED
ORG BRN
YLW
BLU
GREEN RED
ORANGE BROWN
YELLOW BLUE
NOTE:
GRN RED
ORG BRN
YLW
BLU
C1
GRN/YL
W
FAN SPEED SWITCH
X1M
2
1
3 4
5
L N
L N
F1U
GRN/YL
W
GRN/YL
W
M 1~
Q1M
6
Connect the power supply and remote controller cables to the
terminal.
7
Attach the terminal cover and fix the power supply cable with
the cable holder.
5.4
Connecting the drain piping
5.4.1
To install the drain piping to the unit
Horizontal installation
a
b
Vertical installation
a
b
Keep piping as short as possible and slope it downwards at a
gradient of at least 1/100 so that air does not remain trapped inside
the pipe.
5.4.2
To check the drain piping
After the drain piping work is finished, check if drainage flows
smoothly.