9
Attach insulation sleeve
Round crimp-style terminal
Electric wire
Connect wires of the
same gauge to both side.
Do not connect wires of the
same gauge to one side.
Do not connect wires
of different gauges.
Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screw.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
•
•
•
•
All wires must be firmly connected.
Make sure all the wire do not touch the refrigerant pipings, or any moving parts.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly fixed to avoid any gap.
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
•
•
•
•
•
•
Operating Limits:
Thermal carrier : Water
Entering Water Temperature : 4°C ~ 10°C (Cooling)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
OPERATING RANGE
Temperature
Ts °C/°F
Th °C/°F
Minimum indoor
temperature
19.0 / 66.2
14.0 / 57.2
Maximum indoor
temperature
32.0 / 89.6
23.0 / 73.4
Ts: Dry bulb temperature. Th: Wet bulb temperature.
Model (FWC)
Indoor
02G
03G
04G
06G
08G
10G
Voltage Range**
Indoor
220V-240V/ ~ /50Hz +
!
or 208V-230V/ ~ /60Hz +
!
Power Supply Cable Size*
mm
2
Number of Conductors
1.0
5 or 6
Recommended Time Delay Fuse*
A
6
6
6
6
6
6
Model (FWC)
Indoor
12G
14G
16G
18G
20G
Voltage Range**
Indoor
220V-240V/ ~ /50Hz +
!
or 208V-230V/ ~ /60Hz +
!
Power Supply Cable Size*
mm
2
Number of Conductors
1.0
5
1.0
5
1.0
5
1.0
5
Recommended Time Delay Fuse*
A
6
6
6
6
6
Note:
This is a proposed wiring connection. It may change subject to the chiller unit and must comply with the local and national
code and regulations.
1.0
5 or 6
1.0
5 or 6
1.0
5 or 6
1.0
5 or 6
1.0
5 or 6
1.0
5 or 6