9

Attach insulation sleeve

Round crimp-style terminal

Electric wire

Connect wires of the 
same gauge to both side.

Do not connect wires of the 
same gauge to one side.

Do not connect wires 
of different gauges.

Use the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screw.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.




All wires must be firmly connected.
Make sure all the wire do not touch the refrigerant pipings, or any moving parts.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly fixed to avoid any gap.
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching 
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).






Operating Limits:

Thermal carrier : Water
Entering Water Temperature : 4°C ~ 10°C (Cooling)
Maximum water pressure : 16 bar
Air temperature : (as below)

Cooling Mode

OPERATING RANGE

Temperature

Ts °C/°F

Th °C/°F

Minimum indoor 

temperature

19.0 / 66.2

14.0 / 57.2

Maximum indoor 

temperature

32.0 / 89.6

23.0 / 73.4

Ts: Dry bulb temperature.           Th: Wet bulb temperature.

Model  (FWC)

Indoor

02G

03G

04G

06G

08G

10G

Voltage Range**

Indoor

220V-240V/ ~ /50Hz + 

!    

or    208V-230V/ ~ /60Hz + 

Power Supply Cable Size* 

mm

2

Number of Conductors

   1.0

5 or 6

 

Recommended Time Delay Fuse* 

6

Model  (FWC)

Indoor

12G

14G

16G

18G

20G

Voltage Range**

Indoor

220V-240V/ ~ /50Hz + 

!    

or    208V-230V/ ~ /60Hz + 

Power Supply Cable Size* 

mm

2

Number of Conductors

1.0

5

1.0

5

1.0

5

1.0

5

Recommended Time Delay Fuse* 

A

6

6

6

6

6

Note:

This is a proposed wiring connection. It may change subject to the chiller unit and must comply with the local and national 
code and regulations.

   1.0

5 or 6

   1.0

5 or 6

   1.0

5 or 6

   1.0

5 or 6

   1.0

5 or 6

   1.0

5 or 6

Содержание FWC02G

Страница 1: ...FAN COIL UNIT G SERIES IM CCGW 0821 5 DAIKIN Part Number R08019045598 Installation Manual Chilled Water Fan Coil Unit English MODELS FWC02G FWC03G FWC04G FWC06G FWC08G FWC10G FWC12G FWC14G FWC16G FWC...

Страница 2: ...6 0 CONDENSATE DRAIN R3 4 198 267 KD KC 187 43 104 161 219 461 132 KE 38 66 110 18 18 16 143 38 27 30 82 148 251 FWC02G WATER OUT 3 4 BSPT FEMALE THREADADAPTOR WATER IN 3 4 BSPT FEMALE THREADADAPTOR M...

Страница 3: ...74 155 18 16 248 119 143 328 363 25 660 175 109 KC KB 49 37 75 KA OUT IN 198 KE 187 43 104 18 143 27 161 219 251 18 148 132 110 38 26 267 KC 38 KB KA 16 59 WATER OUT 1 BSPT FEMALE THREADADAPTOR 142 WA...

Страница 4: ...78 1300 1354 1392 1298 14G 1142 1116 953 877 929 930 836 16 18G 1280 1254 1091 1015 1067 1068 974 20G 1420 1394 1231 1155 1207 1208 1114 FWC14 16 18 20G 12 203 59 12 KG 59 KF 24 363 KE KD KC KB KA 43...

Страница 5: ...or use in room where mineral oil oil vapour or oil steam exist this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen keep f...

Страница 6: ...ong to withstand the weight 300mm or more 300mm or more Can be smaller than 300mm if ceiling is removable Floor 2300mm or more Ceiling Insulation material field supply 300mm or more Air outlet side Se...

Страница 7: ...se contaminated or damaged pipe and fitting for installation Some main fitting components are needed in the system to enhance the capacity and ease of service such as gate valve balancing valve 2 way...

Страница 8: ...08 230V 60Hz TH 220 240V 50Hz or 208 230V 60Hz 220 240V 50Hz or 208 230V 60Hz TH FSC FSC FL FM FH N FL FM FH N L N L N L N FL Fan Low FM Fan Medium FH Fan High N Neutral FSC Fan Speed Controller X1 X2...

Страница 9: ...er means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the relevant local and national legislation 7 2 8 1 2 2 8 2 2 8 0 1 2 3...

Страница 10: ...g wires to the power supply terminal block Connect the wires by matching to the indication on terminal block Refer to the wiring diagram attached on the unit Operating Limits Thermal carrier Water Ent...

Страница 11: ...ion guide for such unit The installation of fan coil unit may vary according to the type of outdoor unit Installation must be done by qualified personnel who is familiar with this type of product Ensu...

Страница 12: ...the Adaptor Holder INTERCHANGEABLE HEAT EXCHANGER PIPING DIRECTION GUIDE LINE The simulation below is based on FCU FWC G Unit From right piping direction to left piping direction To perform this simu...

Страница 13: ...ow the Hairpin move out and not touching the Side Panel MOVE UPWARDS STEP 7 While holding Heat Exchanger gently move out the Heat Exchanger Distributor from the Side Panel Please be aware of the relea...

Страница 14: ...pe is at the same side with the Adaptor Holder STEP 14 The changing of Heat Exchanger Pipe Direction is completed STEP 10 Then gently pull the Side Panel outwards to allow the Hairpin side of the Heat...

Страница 15: ...it 4 Switch off unit and call local dealer serviceman If the fault persists please call your local dealer serviceman SERVICE AND MAINTENANCE CAUTION Avoid direct contact of any coil treatment cleaners...

Страница 16: ...nato ku Tokyo 108 0075 Japan http www daikin com global Lot 10 Jalan Perusahaan 8 Kawasan Perusahaan Pekan Banting 42700 Banting Selangor D E Malaysia The manufacturer reserves the right to revise any...

Отзывы: