1-10
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (Heating),
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Heating Mode
Ts: Dry bulb temperature. Th: Wet bulb temperature.
OPERATING RANGE
Temperature
Ts °C/°F
Th °C/°F
Minimum indoor
temperature
19.0 / 66.2
14.0 / 57.2
Maximum indoor
temperature
32.0 / 89.6
23.0 / 73.4
Temperature
Ts °C/°F
Th °C/°F
Minimum indoor
temperature
15.0 / 59.0
-
Maximum indoor
temperature
27.0 / 80.6
-
OVERALL CHECKING
Note:
The installation guide above covers only the fan coil unit. For installation of outdoor (mini chiller etc) please refer to
the installation guide for such unit.
The installation of fan coil unit may vary according to the type of outdoor unit.
Installation must be done by qualified personnel who is familiar with this type of product.
•
•
•
SERVICE AND MAINTENANCE
!
CAUTION
Avoid direct contact of any coil treatment cleaners on plastic part. This may cause plastic part to deform as a
result of chemical reaction.
Service Parts
Maintenance Procedures
Period
Indoor Air Filter
Remove any dust adhered on the filter by using a vacuum cleaner or wash
in lukewarm water (below 40°C) with neutral cleaning detergent.
Rinse well and dry the filter before placing it back onto the unit.
Do not use gasoline, volatile substances or chemical to clean the filter.
1.
2.
3.
At least once every
2 weeks.
More frequently
if necessary.
Indoor Unit
Clean any dirt or dust on the grille or panel by wiping it using soft cloth
soaked in lukewarm water (below 40°C) with neutral detergent solution.
Do not use gasoline, volatile substances or chemical to clean the indoor
unit.
1.
2.
At least once every
2 weeks.
More frequently
if necessary.
Ensure that:
The unit has been mounted solidly and rigid in
position.
The piping and connections are leak-proof.
Proper wiring has been installed.
Drainage check
pour some water into the left side of the drain pan (the
drainage is at the right side of the unit).
•
1)
2)
3)
•
–
Test run:
Conduct a test run on the unit after having perform the
water drainage test and the gas leakage test.
Check the following items:
Is the electrical plug inserted firmly into the socket?
Is there any abnormal sounds from the unit?
Is there any abnormal vibrations on the unit or the
piping?
Is the drainage of water smooth?
Confirm that:
The evaporator blower is running and discharge cool
air.
•
1)
2)
a)
b)
c)
d)
•
1)
Note is valid for Turkey only: The lifetime of our products is ten (10) years
1 IM-SBBW-0314(1)DAIKIN-EN.indd 10
1 IM-SBBW-0314(1)DAIKIN-EN.indd 10
1/9/15 9:38:55 AM
1/9/15 9:38:55 AM
Содержание FUD20B
Страница 14: ...MEMO 1 IM SBBW 0314 1 DAIKIN EN indd 12 1 IM SBBW 0314 1 DAIKIN EN indd 12 1 9 15 9 38 55 AM 1 9 15 9 38 55 AM...
Страница 74: ...M TKA 6 IM SBBW 0314 1 DAIKIN RU indd 12 6 IM SBBW 0314 1 DAIKIN RU indd 12 1 9 15 9 44 32 AM 1 9 15 9 44 32 AM...
Страница 86: ...NOT 7 IM SBBW 0314 1 DAIKIN TR indd 12 7 IM SBBW 0314 1 DAIKIN TR indd 12 1 9 15 9 44 49 AM 1 9 15 9 44 49 AM...
Страница 87: ...CVR IM SBBW 0314 2 DAIKIN EN 4013 3 CVR IM SBBW 0314 2 DAIKIN EN 4013 3 3 24 16 9 17 14 AM 3 24 16 9 17 14 AM...
Страница 88: ...CVR IM SBBW 0314 2 DAIKIN EN 4014 4 CVR IM SBBW 0314 2 DAIKIN EN 4014 4 3 24 16 9 17 15 AM 3 24 16 9 17 15 AM...
Страница 91: ...0 IM SBBW 0314 0 DAIKIN AR indd 12 0 IM SBBW 0314 0 DAIKIN AR indd 12 1 9 15 9 42 12 AM 1 9 15 9 42 12 AM...
Страница 98: ...0 IM SBBW 0314 0 DAIKIN AR indd 5 0 IM SBBW 0314 0 DAIKIN AR indd 5 1 9 15 9 42 15 AM 1 9 15 9 42 15 AM...
Страница 103: ...CVR IM SBBW 0314 2 DAIKIN AR 4012 2 CVR IM SBBW 0314 2 DAIKIN AR 4012 2 3 24 16 9 16 53 AM 3 24 16 9 16 53 AM...