SiBE01-503
Troubleshooting
Service Diagnosis
63
4.6
High
Pressure Control in Cooling
Remote
Controller
Display
F6
Method of
Malfunction
Detection
High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the
temperature being sensed by the heat exchanger thermistor exceeds the limit.
Malfunction
Decision
Conditions
Activated when the temperature being sensed by the heat exchanger thermistor rises above
63°C (RYN models) or 65°C (ARY models).
Deactivated when the temperature drops below 48°C (RYN models) or 50°C (ARY models).
Supposed
Causes
The installation space is not large enough.
Faulty outdoor unit fan
Faulty heat exchanger thermistor
Faulty stop valve
Dirty heat exchanger
Содержание FTYN25DV3B ATY20DV2
Страница 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump...
Страница 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii...
Страница 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2...
Страница 13: ...Functions SiBE01 503 4 List of Function...
Страница 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6...
Страница 21: ...Printed Circuit Board Connector Wiring Diagram SiBE01 503 12 Printed Circuit Board Connector Wiring Diagram...
Страница 35: ...Control Specification SiBE01 503 26 Functions and Control...
Страница 59: ...Instructions SiBE01 503 50 System Configuration...
Страница 79: ...Check SiBE01 503 70 Service Diagnosis...
Страница 117: ...Others SiBE01 503 108 Others...