Service Check Function
SiBE01-503
54
Service Diagnosis
3. Service Check Function
The temperature display sections on the main unit indicate corresponding codes.
Check Method 1
1. When the timer cancel button is held down for 5 seconds, a “00” indication flashes on the
temperature display section.
2. Press the timer cancel button repeatedly until a continuous beep is produced.
The code indication changes in the sequence shown below, and notifies with a long beep.
Note:
1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To cancel the code display, hold the timer cancel button down for 5 seconds. The code
display also cancels itself if the button is not pressed for 1 minute.
No.
Code
No.
Code
No.
Code
1
00
12
F6
23
A1
2
U4
13
C7
24
E1
3
L5
14
A3
25
UA
4
E6
15
H8
26
UH
5
H6
16
H9
27
P4
6
H0
17
C9
28
L3
7
A6
18
C4
29
L4
8
E7
19
C5
30
H7
9
U0
20
J3
31
U2
10
F3
21
J6
32
EA
11
A5
22
E5
33
AH
(R4759)
TIMER CANCEL button
It cancels the timer setting.
Содержание FTYN25DV3B ATY20DV2
Страница 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump...
Страница 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii...
Страница 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2...
Страница 13: ...Functions SiBE01 503 4 List of Function...
Страница 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6...
Страница 21: ...Printed Circuit Board Connector Wiring Diagram SiBE01 503 12 Printed Circuit Board Connector Wiring Diagram...
Страница 35: ...Control Specification SiBE01 503 26 Functions and Control...
Страница 59: ...Instructions SiBE01 503 50 System Configuration...
Страница 79: ...Check SiBE01 503 70 Service Diagnosis...
Страница 117: ...Others SiBE01 503 108 Others...