Part 3. Repair
3.3. Unit specific repair procedures
Page 72
19/08/19
|
Version 1.1
Optimized Heating 4
3.3.1.2. Replacing humidity sensor
PRELIMINARY ACTIONS
1. Switch off the Daikin unit via the user interface.
2. Switch off the Daikin unit with the field supplied circuit breaker.
3. Remove plate work when required, refer to
.
PROCEDURE
Removal
1. Disconnect the humidity sensor connector from the indoor unit PCB.
2. Carefully click the complete humidity sensor PCB assembly (1) out of the indoor unit.
Figure 3-5: Removing the humidity sensor PCB assembly
Installation
1. Click the humidity sensor PCB assembly on the indoor unit.
Figure 3-6: Installing the humidity sensor PCB assembly
2. Route the humidity sensor harness inside the switch box, along the harness retainers.
1. Humidity sensor PCB assembly
1. Humidity sensor PCB assembly