ESIE17-19C
|
Part 2. Troubleshooting
2.4. Component checklist
Page 56
19/08/19
|
Version 1.1
Optimized Heating 4
2.4.2.5. Main PCB
Not applicable.
PRELIMINARY ACTIONS
1. Switch off the Daikin unit via the user interface.
2. Switch off the Daikin unit with the field supplied circuit breaker.
3. Remove plate work when required (refer to
).
PROCEDURE
1. Switch on the Daikin unit with the field supplied circuit breaker.
2. Switch on the Daikin unit via the user interface.
3. Check if the HAP LED is blinking in regular intervals (1/0.5 sec), if not blinking, replace the main PCB board (refer to
).
4. Measure the supply voltage to the main PCB board: there should be ± 220 V between brown and blue cable. If not correct
voltage, replace the electrical noise filter PCB (refer to
"Replacing electrical noise filter" on page 80
).
5. Switch off the Daikin unit via the user interface.
6. Switch off the Daikin unit with the field supplied circuit breaker.
7. Remove plate work when required.
8. Open the compressor insulation.
9. Remove the terminal cover of compressor wiring.
10. Measure the voltage on S70: pin 7-4 and wait until it drops below 10 VDC.
11. Disconnect the compressor wires and connect the compressor wires to the Inverter Analyzer (SPP number 1368521).
Technical specification
Description
Location
Piping diagram
Wiring diagram
Switch box
Component overview of unit
.
.
See
Check procedure
Mechanical check
Electrical check
W
ARNING
: R
ISK
OF
ELECTROCUTION
The smoothing capacitor must discharge below 10 VDC before removing the compressor wiring.
I
NFORMATION
Note the position of the cables on the compressor wire terminals to allow identical wiring during reinstallation.