ESIE17-19C
|
Part 5. Appendix
5.1. Field setting
Optimized Heating 4
Page 110
19/08/19
|
Version 1.1
5.1.3.3.2 Remote controller ARC480A11
Figure 5-6: How to adjust target set temperature in heating operation - Remote controller: ARC480A11
5.1.3.4. Set unit in inverter checker mode
Activate power transistor test operation from the indoor unit
1. Turn the power on.
2. Please select trial operation “FAN ONLY” by R/C.
Note: trial operation described in each installation manual
3. Start the power transistor test operation.
Temp
Temp
OFF
SC
FAN
FAN
FAN
Temp
Temp
0
1
2
3
4
Select
“SU”
Select “7”
DISPLAY NORMAL
AFTER 60 sec
Display
Select
Send signal to indoor unit
Adjust target set temperature
0: -2.0°C
1: -1.0°C
2: ±0 (factory setting)
3: +1.0°C
4: +2.0°C
Select