5 Preparation

Installer reference guide

9

FTXTA30A2V1BW
Split system air conditioner
4P518023-6E – 2019.04

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

5.2.1

Installation site requirements of the
indoor unit

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

INFORMATION

The sound pressure level is less than 70 dBA.

Air flow.

 Make sure nothing blocks the air flow.

Drainage.

  Make  sure  condensation  water  can  be  evacuated

properly.

Wall insulation

. When conditions in the wall exceed 30°C and a

relative  humidity  of  80%,  or  when  fresh  air  is  inducted  into  the
wall,  then  additional  insulation  is  required  (minimum  10  mm
thickness, polyethylene foam).

Wall  strength. 

Check  whether  the  wall  or  the  floor  is  strong

enough to support the weight of the unit. If there is a risk, reinforce
the wall or the floor before installing the unit.

Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
3 metres may NOT be sufficient.

▪ Choose a location where the hot/cold air discharged from the unit

or the operation noise, will NOT disturb anyone.

Fluorescent lights

. When installing a wireless user interface in a

room  with  fluorescent  lights,  mind  the  following  to  avoid
interference:

▪ Install  the  wireless  user  interface  as  close  as  possible  to  the

indoor unit.

▪ Install  the  indoor  unit  as  far  as  possible  from  the  fluorescent

lights.

It  is  NOT  recommended  to  install  the  unit  in  the  following  places
because it may shorten the life of the unit:

▪ Where the voltage fluctuates a lot

▪ In vehicles or vessels

▪ Where acidic or alkaline vapour is present

▪ In  places  where  a  mineral  oil  mist,  spray  or  vapour  may  be

present  in  the  atmosphere.  Plastic  parts  may  deteriorate  and  fall
off or cause water leakage.

▪ In places where the unit would be in the path of direct sunlight.

▪ In bathrooms.

▪ Sound  sensitive  areas  (e.g.  near  a  bedroom),  so  that  the

operation noise will cause no trouble.

WARNING

Do NOT place objects below the indoor and/or outdoor unit
that  may  get  wet.  Otherwise  condensation  on  the  unit  or
refrigerant pipes, air filter dirt or drain blockage may cause
dripping,  and  objects  under  the  unit  may  get  dirty  or
damaged.

Spacing. 

Install the unit at least 1.8 m from the floor and keep the

following  requirements  in  mind  for  distances  from  the  walls  and
the ceiling:

≥50

≥50

≥30

(mm)

Note: 

 Make sure that there are no obstacles within 500 mm under

the signal receiver. They may influence reception performance of the
user interface.

5.3

Preparing refrigerant piping

5.3.1

Refrigerant piping requirements

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

L1 liquid piping

Ø6.4 mm

L1 gas piping

Ø9.5 mm

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

Annealed (O)

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

5.3.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

Содержание FTXTA30A2V1BW

Страница 1: ...Installer reference guide Split system air conditioner English Installer reference guide Split system air conditioner FTXTA30A2V1BW...

Страница 2: ...4 4 Pipe bending guidelines 16 6 4 5 To flare the pipe end 16 6 4 6 To connect the refrigerant piping to the indoor unit 16 6 5 Connecting the electrical wiring 16 6 5 1 About connecting the electric...

Страница 3: ...ted on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the product cont...

Страница 4: ...m Floor standing units 1 8 x 2 2 m Wall mounted units 2 2 m Ceiling mounted units 3 Use the graph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160...

Страница 5: ...e legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case recharge is required see the nameplate of...

Страница 6: ...nt carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the curr...

Страница 7: ...do and know to install the system Configuration What to do and know to configure the system after it is installed Commissioning What to do and know to commission the system after it is configured Han...

Страница 8: ...53 EU This unit is considered as combined equipment according to the definition of Directive 2014 53 EU 4 3 1 Precautions when using the wireless adapter Do NOT use near Medical equipment E g persons...

Страница 9: ...vapour may be present in the atmosphere Plastic parts may deteriorate and fall off or cause water leakage In places where the unit would be in the path of direct sunlight In bathrooms Sound sensitive...

Страница 10: ...o the fixed wiring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING ALWAYS use multicore cable for power supply cables 6 Installation...

Страница 11: ...Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover NOTICE When closing the service cover make sure that the tightening torque does NOT exceed 1 4 0 2...

Страница 12: ...ooks 1 2 b a c c a Screw b Electrical wiring box c Rear hook 5 To re install the cover first attach the electrical wiring box to the hooks close the electrical wiring box and re install the screw NOTI...

Страница 13: ...rial field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a...

Страница 14: ...so it will NOT be pulled out of the drain pipe 50 mm To connect the piping on right side right back or right bottom INFORMATION The factory default is right side piping For left side piping remove th...

Страница 15: ...l may dissolve and damage the system NOTICE Take the following precautions on refrigerant piping into account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g...

Страница 16: ...the unit using flare connections Insulation Insulate the refrigerant piping interconnection cable and drain hose on the indoor unit as follows c a b f d g e a Gas pipe b Gas pipe insulation c Interco...

Страница 17: ...of practice 1 Set the indoor unit on the mounting plate hooks Use the marks as a guide c a b d a Mounting plate accessory b Piece of packing material c Interconnection cable d Wire guide INFORMATION S...

Страница 18: ...arking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE Do NOT bend refrigeran...

Страница 19: ...t of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Mak...

Страница 20: ...m The wiring diagram is delivered with the unit located inside of the outdoor unit bottom side of the top plate 11 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring...

Страница 21: ...lled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European national and local directives...

Страница 22: ......

Страница 23: ......

Страница 24: ...4P518023 6E 2019 04 Copyright 2019 Daikin...

Отзывы: