6 Installation

Installer reference guide

14

FTXTA30A2V1BW

Split system air conditioner

4P518023-6E – 2019.04

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe  size.

  If  drain  hose  extension  or  embedded  drain  piping  is

required, use appropriate parts that match the hose front end.

Ø16

Ø18

NOTICE

▪ Install the drain hose with a downward slope.

▪ Traps are NOT permitted.

▪ Do NOT put the end of the hose in water.

Drain  hose  extension.

  To  extend  the  drain  hose,  use  a  field

supplied  hose  with  inner  Ø16  mm.  Do  NOT  forget  to  use  a  heat
insulation tube on the indoor section of the extension hose.

a

a

b

c

Ø16

Ø16

a

Drain hose supplied with the indoor unit

b

Heat insulation tube (field supply)

c

Extension drain hose

Rigid polyvinyl chloride pipe.

 When connecting a rigid polyvinyl

chloride pipe (nominal Ø13 mm) directly to the drain hose as with
embedded piping work, use a field supplied drain socket (nominal
Ø13 mm).

a

b

c

Ø18

a

Drain hose supplied with the indoor unit

b

Drain socket with nominal Ø13 mm (field supply)

c

Rigid polyvinyl chloride pipe (field supply)

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

1

Insert the drain hose in the drain pipe as shown in the following
figure, so it will NOT be pulled out of the drain pipe.

≥50

mm

To connect the piping on right side, right-back, or
right-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Attach the drain hose with adhesive vinyl tape to the bottom of
the refrigerant pipes.

2

Wrap  the  drain  hose  and  the  refrigerant  pipes  together  using
insulation tape.

A

B

a b

A

Right-side piping

B

Right-bottom piping

C

Right-back piping

a

Remove the pipe port cover here for right-side piping.

b

Remove the pipe port cover here for right-bottom piping.

To connect the piping on left side, left-back, or
left-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Remove  the  insulation  fixing  screw  on  the  right  side  and
remove the drain hose.

2

Remove the drain plug on the left side and attach it to the right
side.

NOTICE

Do  NOT  apply  lubricating  oil  (refrigerant  oil)  to  the  drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.

a

a

4 mm hexagonal wrench

3

Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.

a

b

a

b

a

Insulation fixing screw

b

Drain hose

4

Attach the drain hose to the refrigerant pipes bottom side using
adhesive vinyl tape.

A

B

b

a

Содержание FTXTA30A2V1BW

Страница 1: ...Installer reference guide Split system air conditioner English Installer reference guide Split system air conditioner FTXTA30A2V1BW...

Страница 2: ...4 4 Pipe bending guidelines 16 6 4 5 To flare the pipe end 16 6 4 6 To connect the refrigerant piping to the indoor unit 16 6 5 Connecting the electrical wiring 16 6 5 1 About connecting the electric...

Страница 3: ...ted on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the product cont...

Страница 4: ...m Floor standing units 1 8 x 2 2 m Wall mounted units 2 2 m Ceiling mounted units 3 Use the graph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160...

Страница 5: ...e legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case recharge is required see the nameplate of...

Страница 6: ...nt carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the curr...

Страница 7: ...do and know to install the system Configuration What to do and know to configure the system after it is installed Commissioning What to do and know to commission the system after it is configured Han...

Страница 8: ...53 EU This unit is considered as combined equipment according to the definition of Directive 2014 53 EU 4 3 1 Precautions when using the wireless adapter Do NOT use near Medical equipment E g persons...

Страница 9: ...vapour may be present in the atmosphere Plastic parts may deteriorate and fall off or cause water leakage In places where the unit would be in the path of direct sunlight In bathrooms Sound sensitive...

Страница 10: ...o the fixed wiring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING ALWAYS use multicore cable for power supply cables 6 Installation...

Страница 11: ...Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover NOTICE When closing the service cover make sure that the tightening torque does NOT exceed 1 4 0 2...

Страница 12: ...ooks 1 2 b a c c a Screw b Electrical wiring box c Rear hook 5 To re install the cover first attach the electrical wiring box to the hooks close the electrical wiring box and re install the screw NOTI...

Страница 13: ...rial field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a...

Страница 14: ...so it will NOT be pulled out of the drain pipe 50 mm To connect the piping on right side right back or right bottom INFORMATION The factory default is right side piping For left side piping remove th...

Страница 15: ...l may dissolve and damage the system NOTICE Take the following precautions on refrigerant piping into account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g...

Страница 16: ...the unit using flare connections Insulation Insulate the refrigerant piping interconnection cable and drain hose on the indoor unit as follows c a b f d g e a Gas pipe b Gas pipe insulation c Interco...

Страница 17: ...of practice 1 Set the indoor unit on the mounting plate hooks Use the marks as a guide c a b d a Mounting plate accessory b Piece of packing material c Interconnection cable d Wire guide INFORMATION S...

Страница 18: ...arking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE Do NOT bend refrigeran...

Страница 19: ...t of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Mak...

Страница 20: ...m The wiring diagram is delivered with the unit located inside of the outdoor unit bottom side of the top plate 11 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring...

Страница 21: ...lled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European national and local directives...

Страница 22: ......

Страница 23: ......

Страница 24: ...4P518023 6E 2019 04 Copyright 2019 Daikin...

Отзывы: