8 Commissioning

Installer reference guide

19

FTXTA30A2V1BW
Split system air conditioner
4P518023-6E – 2019.04

a

a

Address jumper J4

NOTICE

Be  careful  NOT  to  damage  any  of  the  surrounding  parts
when cutting the address jumper.

3

Turn the power supply on.

4

Press 

 and 

 simultaneously.

5

Press 

, select   and press 

.

Result: 

The operation lamp will start to blink.

a

a

Indoor unit ON/OFF switch and operation lamp

6

Press  the  indoor  unit  ON/OFF  switch  while  the  operation  lamp
is blinking.

Address jumper

Address

Factory setting

1

After cutting with nippers

2

INFORMATION

If the setting could NOT be completed while the operation
lamp  was  blinking,  repeat  the  setting  process  from  the
beginning.

7

When the setting is complete, keep 

 pressed for at least

5 seconds.

Result: 

 The user interface will return to the previous screen.

8

Commissioning

8.1

Overview: Commissioning

This  chapter  describes  what  you  have  to  do  and  know  to
commission the system after it is installed.

Typical workflow

Commissioning typically consists of the following stages:

1

Checking the "Checklist before commissioning".

2

Performing a test run for the system.

8.2

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all  below  checks  are  fulfilled,  the  unit  MUST  be  closed,  ONLY  then
can the unit be powered up.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

The 

outdoor unit

 is properly mounted.

Air inlet/outlet

Check  that  the  air  inlet  and  outlet  of  the  unit  is  NOT
obstructed  by  paper  sheets,  cardboard,  or  any  other
material.

There are NO 

missing phases

 or 

reversed phases

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

Drainage

Make sure drainage flows smoothly.

Possible consequence: 

Condensate water might drip.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

The  specified  wires  are  used  for  the 

interconnection

cable

.

The indoor unit receives the signals of the 

user interface

.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

The 

insulation resistance

 of the compressor is OK.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

8.3

To perform a test run

Prerequisite: 

Power supply MUST be in the specified range.

Prerequisite: 

Test  run  may  be  performed  in  cooling  or  heating

mode.

Prerequisite: 

Test run should be performed in accordance with the

operation  manual  of  the  indoor  unit  to  make  sure  that  all  functions
and parts are working properly.

1

In  cooling  mode,  select  the  lowest  programmable  temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.

2

When  the  test  run  is  finished,  set  the  temperature  to  a  normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.

3

The  system  stops  operating  3  minutes  after  the  unit  is  turned
OFF.

Содержание FTXTA30A2V1BW

Страница 1: ...Installer reference guide Split system air conditioner English Installer reference guide Split system air conditioner FTXTA30A2V1BW...

Страница 2: ...4 4 Pipe bending guidelines 16 6 4 5 To flare the pipe end 16 6 4 6 To connect the refrigerant piping to the indoor unit 16 6 5 Connecting the electrical wiring 16 6 5 1 About connecting the electric...

Страница 3: ...ted on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the product cont...

Страница 4: ...m Floor standing units 1 8 x 2 2 m Wall mounted units 2 2 m Ceiling mounted units 3 Use the graph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160...

Страница 5: ...e legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case recharge is required see the nameplate of...

Страница 6: ...nt carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the curr...

Страница 7: ...do and know to install the system Configuration What to do and know to configure the system after it is installed Commissioning What to do and know to commission the system after it is configured Han...

Страница 8: ...53 EU This unit is considered as combined equipment according to the definition of Directive 2014 53 EU 4 3 1 Precautions when using the wireless adapter Do NOT use near Medical equipment E g persons...

Страница 9: ...vapour may be present in the atmosphere Plastic parts may deteriorate and fall off or cause water leakage In places where the unit would be in the path of direct sunlight In bathrooms Sound sensitive...

Страница 10: ...o the fixed wiring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING ALWAYS use multicore cable for power supply cables 6 Installation...

Страница 11: ...Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover NOTICE When closing the service cover make sure that the tightening torque does NOT exceed 1 4 0 2...

Страница 12: ...ooks 1 2 b a c c a Screw b Electrical wiring box c Rear hook 5 To re install the cover first attach the electrical wiring box to the hooks close the electrical wiring box and re install the screw NOTI...

Страница 13: ...rial field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a...

Страница 14: ...so it will NOT be pulled out of the drain pipe 50 mm To connect the piping on right side right back or right bottom INFORMATION The factory default is right side piping For left side piping remove th...

Страница 15: ...l may dissolve and damage the system NOTICE Take the following precautions on refrigerant piping into account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g...

Страница 16: ...the unit using flare connections Insulation Insulate the refrigerant piping interconnection cable and drain hose on the indoor unit as follows c a b f d g e a Gas pipe b Gas pipe insulation c Interco...

Страница 17: ...of practice 1 Set the indoor unit on the mounting plate hooks Use the marks as a guide c a b d a Mounting plate accessory b Piece of packing material c Interconnection cable d Wire guide INFORMATION S...

Страница 18: ...arking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE Do NOT bend refrigeran...

Страница 19: ...t of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Mak...

Страница 20: ...m The wiring diagram is delivered with the unit located inside of the outdoor unit bottom side of the top plate 11 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring...

Страница 21: ...lled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European national and local directives...

Страница 22: ......

Страница 23: ......

Страница 24: ...4P518023 6E 2019 04 Copyright 2019 Daikin...

Отзывы: